8-4. Outdoor Fan Speed Control (Except SAP–C92)
●
To optimize performance of the air conditioner, the outdoor fan speed is switched automatically according to the
outdoor temperature.
●
If the outdoor air temperature falls below 28.5°C, the fan speed switches to LOW.
●
If the outdoor air temperature rises above 31.5°C, the fan speed switches to HIGH.
●
This function does not become active in heating operation.
H
H
L
31.5
28.5
Outdoor air
temperature (
°
C)
Outdoor fan
speed