12
2-5.
Diagram of
O
utdoor Unit Installation
N
ever install only a single indoor unit.
Be sure to connect indoor and outdoor units only in
combinations that are listed in the catalog or in the
combination table that was provided with the outdoor unit.
(Use caution. Connecting any other model may result in
operation failure and malfunction.)
The dimensions indicated by
in the figure below are
spaces that are required in order to maintain
performance. Install in a location where the dimensions
indicated by
are ensured, and where 2 or more faces
of the unit are unobstructed. In principle, the top direction
should be unobstructed.
Indoor unit C
Indoor unit B
Indoor unit A
Indoor unit D
Service space
Power breaker
Ground
wire
(not
provided)
Ensure 6"(15cm)
of space if a
drain hose is to
be used.
Base (not provided)
(concrete or similar material)
Fasten with anchor bolts
(not provided)
(3/8" or M10, 4 locations)
A
B
C
D
Access panel C
Over 10"(25cm)
Over 8"(20cm)
Over 4"(10cm)
Over 1'8"(50cm)
Fig. 7
07-155 CMH1972-3172 6/6/07 9:34 AM Page 12