13
WM – 700699
CM3212 / KMS1812
Remarks:
Rating conditions are: Outside air temperature 95°F DB/75°F WB
Indoor unit entering air temperature 80°F DB/67°F WB
Performance at
Indoor Units
Outdoor Unit
Complete Unit
230/208V – 1ø – 60Hz
Fan Motor
Compressor
Rating Conditions
A
0.55 / 0.54
1.45 / 1.42
9.80 / 10.64
11.8 / 12.6
W
124 / 108
330 / 290
2,246 / 2,202
2,700 / 2,600
Locked-Rotor Amperes
A
0.19 + 0.45 / 0.18 + 0.40
1.95 / 1.77
22 + 54
—
Performance at
Indoor Units
Outdoor Unit
Complete Unit
230/208V – 1ø – 60Hz
Fan Motor
Compressor
Rating Conditions
A
0.70 / 0.68
1.45 / 1.42
12.85 / 13.90
15.0 / 16.0
W
158 / 136
330 / 290
2,912 / 2,874
3,400 / 3,300
Locked-Rotor Amperes
A
0.19 + 0.19 + 0.45 / 0.18 + 0.18 + 0.40
1.95 / 1.77
22 + 22 + 54
—
CM3212 / KMS7012
×
2+KMS1812
Remarks:
Rating conditions are: Outside air temperature 95°F DB/75°F WB
Indoor unit entering air temperature 80°F DB/67°F WB