Indoor Unit
:
KHS1271
Outdoor Unit :
CH1271
Power Supply : 115V Single Phase 60Hz
< Heating Capacity >
TH : Total Heating Capacity (BTU/h)
1. Rating conditions (#) : Indoor Unit Entering Air Temp. 70 °F (21.1 °C) D.B.
: Outdoor Ambient Temp. 47 °F (8.3 °C) D.B. / 43 °F (6.1 °C) W.B.
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
NOTE
RATING CAPACITY:
14,300 BTU/h
AIR FLOW RATE:
312 CFM
OUTDOOR
INDOOR
ENT. TEMP.
o
F (
o
C)
AMBIENT TEMP.
o
F (
o
C)
W.B.
60
65
70
75
80
(15.6)
(18.3)
(21.1)
(23.9)
(26.7)
0 (-17.8)
TH
8,010
8,000
7,980
7,960
7,930
3 (-16.1)
TH
8,280
8,270
8,250
8,230
8,200
8 (-13.3)
TH
8,930
8,910
8,890
8,870
8,840
13 (-10.6)
TH
9,600
9,580
9,560
9,530
9,500
18 (-7.8)
TH
10,330
10,310
10,290
10,260
10,220
23 (-5.0)
TH
11,100
11,080
11,050
11,020
10,980
28 (-2.2)
TH
11,900
11,870
11,840
11,800
11,760
33 (0.6)
TH
12,720
12,690
12,660
12,610
12,560
38 (3.3)
TH
13,530
13,500
13,460
13,410
13,360
43 (6.1)
TH
14,380
14,350
# 14,300
14,250
14,190
48 (8.9)
TH
15,240
15,200
15,150
15,090
15,020
53 (11.7)
TH
16,090
16,050
15,990
15,920
15,850
58 (14.4)
TH
16,910
16,850
16,790
16,720
16,640
63 (17.2)
TH
17,730
17,670
17,600
17,520
16,690
65 (18.3)
TH
18,040
17,980
17,910
17,480
16,620