background image

IMPORTANT

These air conditioners employ new

refrigerant R410A.

Pay special attention when

servicing the unit.

TECHNICAL & SERVICE MANUAL

K CH0971

K CH1271

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

Indoor Unit

Destination: North America

Outdoor Model No.

CH0971
CH1271

Product Code No.

1 852 330 21
1 852 330 22

Outdoor Unit

KHS0971

KHS1271

CH0971

CH1271

REFERENCE NO. 

SM

700647-06

Indoor Model No.

KHS0971
KHS1271

Product Code No.

1 852 099 79
1 852 099 80

FILE NO.

Содержание CH0971

Страница 1: ...L KHS0971 CH0971 KHS1271 CH1271 DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Unit Destination North America Outdoor Model No CH0971 CH1271 Product Code No 1 852 330 21 1 852 330 22 Outdoor Unit KHS0971 KHS1271 CH0971 CH1271 REFERENCE NO SM700647 06 Indoor Model No KHS0971 KHS1271 Product Code No 1 852 099 79 1 852 099 80 FILE NO ...

Страница 2: ...e fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construc...

Страница 3: ...ELECTRICAL DATA 6 1 Electrical Characteristics 6 2 Electric Wiring Diagrams 7 MAINTENANCE 7 1 Address Setting of the Remote Control Unit 7 2 Disconnecting and Connecting Positive Connector for Outdoor Unit 8 FUNCTIONS 8 1 Operation Functions 8 2 Protective Functions 9 TROUBLESHOOTING 9 1 Precautions before Performing Inspection or Repair 9 2 Method of Self Diagnostics 9 3 Checking the Indoor and O...

Страница 4: ...teristics of New Refrigerant R410A 11 2 Checklist before Servicing 11 3 Tools Specifically for R410A 11 4 Tubing Installation Procedures 11 5 In Case of Compressor Malfunction 11 6 In Case Refrigerant is Leaking 11 7 Charging Additional Refrigerant 11 8 Retro Fitting Existing Systems APPENDIX A INSTRUCTION MANUAL APPENDIX B INSTALLATION INSTRUCTIONS 45 46 47 48 49 49 50 52 53 53 A 1 A 2 Page 4 ...

Страница 5: ... 67 F D B 57 F W B 80 F D B 67 F W B _ D B _ W B 1 OPERATING RANGE Maximum Minimum Maximum Minimum 115 F D B 0 F D B 75 F D B 65 F W B 0 F D B Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Cooling Heating 5 ...

Страница 6: ... V A Available Voltage Range Running Amperes Refrigerant Tube Kit Accessories Narrow tube Wide tube Refrigerant inch mm Tube Diameter inch mm 19 8 24 3 2 82 9 0 11 0 0 08 75 0 81 6 6 35 34 0 37 0 0 18 23 5 8 33 11 16 14 1 4 600 856 362 285 825 189 548 720 265 10 1 32 35 7 16 13 25 32 255 900 350 Outdoor Unit Indoor Unit 11 7 32 32 15 32 7 7 16 21 9 16 28 11 32 10 7 16 1 4 6 35 3 8 9 52 ft m Max al...

Страница 7: ...ltage Range Running Amperes Refrigerant Tube Kit Accessories Narrow tube Wide tube Refrigerant inch mm Tube Diameter inch mm 19 8 24 3 2 82 9 0 11 0 0 08 77 2 83 8 6 35 35 0 38 0 0 18 23 5 8 33 11 16 14 1 4 600 856 362 285 825 189 548 720 265 10 1 32 35 7 16 13 25 32 255 900 350 Outdoor Unit Indoor Unit 11 7 32 32 15 32 7 7 16 21 9 16 28 11 32 10 7 16 1 4 6 35 3 8 9 52 ft m Max allowable tubing le...

Страница 8: ...it Fuse Controls Part No Microprocessor 250V 3A CB KHS0971 1 D3 11 16 L24 31 32 D94 L634 RCS 4HVPIS4U Cross Flow AC Motor IBH 884 076 1 4 BRN WHT 57 9 RED WHT 55 2 16 1 200 1 250 Thermal Fuse 266 130 4 5 250 Fan Remote Control Unit Q ty Dia and Length Type inch mm Fan Motor Nominal Output Coil Resistance Rough Measure RPM Cool Heat Type Model Q ty No of Poles Safety Device Type Operating Temp Clos...

Страница 9: ... Control PCB Control Circuit Fuse Controls Part No Microprocessor 250V 3A CB KHS1271 1 D3 11 16 L24 31 32 D94 L634 RCS 4HVPIS4U Cross Flow AC Motor IBH 884 076 1 4 BRN WHT 57 9 RED WHT 55 2 16 1 250 1 250 Thermal Fuse 266 130 4 5 250 Fan Remote Control Unit Q ty Dia and Length Type inch mm Fan Motor Nominal Output Coil Resistance Rough Measure RPM Cool Heat Type Model Q ty No of Poles Safety Devic...

Страница 10: ...hm DC Motor Type Compressor Model Nominal Output Compressor Coil Resistance Ambient Temp 68 F 20 C Ohm DC Rotary Inverter G4C090LU1ER 900W U V V W W U 0 81 0 81 0 81 CT Peak current cut off control Compressor Discharge Temp Control Operation cut off control in abnormal ambient Temp Safety Device Micro F VAC Run Capacitor Crankcase Heater Yes Yes Yes Overload Relay CS 7L115 Model Operation Temp Ope...

Страница 11: ...r Type Compressor Model Nominal Output Compressor Coil Resistance Ambient Temp 68 F 20 C Ohm DC Rotary Inverter G4C090LU1ER 900W U V V W W U 0 81 0 81 0 81 CT Peak current cut off control Compressor Discharge Temp Control Operation cut off control in abnormal ambient Temp Safety Device Micro F VAC Run Capacitor Crankcase Heater Yes Yes Yes Overload Relay CS 7L115 Model Operation Temp Open 239 F 11...

Страница 12: ...104 10 15 20 25 30 35 40 Indoor air temp sensor Model PTM D51H S3 TH2 Indoor heat exchanger sensor Model PTM D51H S3 TH1 Compressor temp sensor Model DTN TKS274Y TH2 Resistance k ohm Resistance k ohm Temperature F C Outdoor air temp sensor Model DTN TKS269B Outdoor heat exchanger sensor Model DTN TKS274Y TH1 40 35 30 25 20 15 10 5 0 4 5 14 23 32 41 50 59 68 20 15 10 5 0 5 10 15 20 Resistance k ohm...

Страница 13: ...3 DIMENSIONAL DATA Indoor Unit KHS0971 KHS1271 Unit inch mm 13 ...

Страница 14: ...D 1 5 1 6 21 3 16 6 3 32 4 9 32 2 5 32 Narrow tube service valve dia 1 4 6 35 Wide tube service valve dia 3 8 9 52 3 19 32 15 32 10 7 16 265 11 13 32 12 7 16 Outdoor Unit CH0971 CH1271 Unit inch mm 28 11 32 720 2 1 8 21 9 16 548 5 8 14 ...

Страница 15: ...t KHS0971 KHS1271 Outdoor Unit CH0971 CH1271 Insulation of Refrigerant Tubing Because capillary tubing is used in the outdoor unit both the wide and narrow tubes of this air conditioner become cold To prevent heat loss and wet floors due to dripping of condensation both tubes must be well insulated with a proper insulation material The thickness of the insulation should be a min 5 16 8 mm After a ...

Страница 16: ...ir temperature F C 8 9 6 5 7 4 145 1 0 159 1 1 173 1 2 131 0 9 117 0 8 Low pressure at wide tube service valve psig MPaG Check each performance value in test run mode Electrical performance values represent a combined indoor outdoor value NOTE Hi Fan Lo fan 4 20 5 15 14 10 23 5 32 0 41 5 50 10 59 15 68 20 77 25 86 30 95 35 104 40 80 F 27 C 75 F 24 C Indoor Air Temp 86 F 30 C 80 F 27 C 75 F 24 C In...

Страница 17: ... F C 493 3 4 421 2 9 348 2 4 276 1 9 High pressure at wide tube service valve psig MPaG 70 F 21 C 63 F 17 C Indoor Air Temp 73 F 23 C 70 F 21 C 63 F 17 C Indoor Air Temp 73 F 23 C 70 F 21 C 63 F 17 C Indoor Air Temp 73 F 23 C Check each performance value in test run mode Electrical performance values represent a combined indoor outdoor value Overload prevention operates to protect the air conditio...

Страница 18: ... F C Operating current A Indoor discharge air temperature F C 12 8 6 10 11 13 7 5 9 4 145 1 0 159 1 1 173 1 2 131 0 9 117 0 8 Low pressure at wide tube service valve psig MPaG Hi Fan Lo fan 4 20 5 15 14 10 23 5 32 0 41 5 50 10 59 15 68 20 77 25 86 30 95 35 104 40 80 F 27 C 75 F 24 C Indoor Air Temp 86 F 30 C 4 20 5 15 14 10 23 5 32 0 41 5 50 10 59 15 68 20 77 25 86 30 95 35 104 40 Hi Fan Lo fan Hi...

Страница 19: ...D B temp F C Indoor discharge air temperature F C 23 5 32 0 41 5 50 10 59 15 68 20 77 25 Outdoor inlet air D B temp F C Indoor Unit KHS1271 Outdoor Unit CH1271 Heating Characteristics RH 46 Indoor fan speed High fan 60Hz 115V Check each performance value in test run mode Electrical performance values represent a combined indoor outdoor value Overload prevention operates to protect the air conditio...

Страница 20: ...00 88 31 1 SHC 9 080 8 800 8 500 8 260 7 890 6 400 TC 9 440 9 160 8 860 8 630 8 250 6 580 72 22 2 SHC 5 770 5 610 5 500 5 390 5 220 4 510 63 76 24 4 SHC 6 700 6 590 6 430 6 370 6 160 5 500 17 2 80 26 7 SHC 7 690 7 580 7 470 7 360 7 200 6 480 84 28 9 SHC 8 680 8 570 8 400 8 300 8 130 6 580 88 31 1 SHC 9 440 9 160 8 860 8 630 8 250 6 580 TC 9 790 9 520 9 220 9 000 8 620 6 740 72 22 2 SHC 4 620 4 450...

Страница 21: ... 970 11 660 11 310 11 050 10 620 8 860 TC 12 370 12 070 11 730 11 480 11 050 9 020 72 22 2 SHC 7 220 7 050 6 880 6 760 6 530 5 620 63 76 24 4 SHC 8 190 8 020 7 850 7 730 7 560 6 590 17 2 80 26 7 SHC 9 220 9 100 8 930 8 820 8 590 7 680 84 28 9 SHC 10 250 10 080 9 900 9 790 9 560 8 650 88 31 1 SHC 11 220 11 050 10 880 10 760 10 590 9 020 TC 12 740 12 450 12 120 11 900 11 470 9 160 72 22 2 SHC 5 900 ...

Страница 22: ...72 22 2 SHC 4 840 4 840 4 840 4 890 4 890 4 890 4 890 63 76 24 4 SHC 5 770 5 770 5 830 5 880 5 880 5 880 5 880 17 2 80 26 7 SHC 6 810 6 810 6 810 6 870 6 870 6 870 6 870 84 28 9 SHC 7 330 7 330 7 420 7 490 7 530 7 540 7 490 88 31 1 SHC 7 330 7 330 7 420 7 490 7 530 7 540 7 490 TC 7 290 7 300 7 450 7 560 7 640 7 680 7 660 72 22 2 SHC 3 580 3 580 3 630 3 690 3 740 3 740 3 740 67 76 24 4 SHC 4 560 4 ...

Страница 23: ... 5 900 5 900 5 960 5 960 5 960 5 960 63 76 24 4 SHC 6 880 6 880 6 930 6 930 6 990 6 990 6 990 17 2 80 26 7 SHC 7 900 7 900 7 960 8 020 8 020 8 020 8 020 84 28 9 SHC 8 930 8 930 8 930 8 990 8 990 8 990 8 990 88 31 1 SHC 9 610 9 620 9 700 9 780 9 840 9 840 9 840 TC 9 460 9 490 9 640 9 770 9 890 9 920 9 970 72 22 2 SHC 4 480 4 480 4 530 4 590 4 650 4 650 4 700 67 76 24 4 SHC 5 450 5 500 5 560 5 620 5...

Страница 24: ...APACITY 12 200 BTU h AIR FLOW RATE 312 CFM OUTDOOR INDOOR ENT TEMP o F o C AMBIENT TEMP o F o C W B 60 65 70 75 80 15 6 18 3 21 1 23 9 26 7 0 17 8 TH 6 910 6 900 6 890 6 870 6 840 3 16 1 TH 7 140 7 130 7 110 7 090 7 070 8 13 3 TH 7 680 7 670 7 660 7 630 7 610 13 10 6 TH 8 250 8 230 8 220 8 190 8 170 18 7 8 TH 8 860 8 850 8 830 8 810 8 780 23 5 0 TH 9 510 9 490 9 470 9 450 9 420 28 2 2 TH 10 180 10...

Страница 25: ...BTU h AIR FLOW RATE 312 CFM OUTDOOR INDOOR ENT TEMP o F o C AMBIENT TEMP o F o C W B 60 65 70 75 80 15 6 18 3 21 1 23 9 26 7 0 17 8 TH 8 010 8 000 7 980 7 960 7 930 3 16 1 TH 8 280 8 270 8 250 8 230 8 200 8 13 3 TH 8 930 8 910 8 890 8 870 8 840 13 10 6 TH 9 600 9 580 9 560 9 530 9 500 18 7 8 TH 10 330 10 310 10 290 10 260 10 220 23 5 0 TH 11 100 11 080 11 050 11 020 10 980 28 2 2 TH 11 900 11 870 ...

Страница 26: ... C Fan speed High Cooling Flap angle 0 Axis air velocity 0 Flap angle 30 Axis air velocity 30 Flap angle 45 Axis air velocity 45 Flap angle 60 Axis air velocity 60 5 5 Air Throw Distance Charts Indoor Unit KHS0971 0 5 10 15 0 5 10 15 20 25 30 Flap angle 0 Axis air velocity 0 Flap angle 30 Axis air velocity 30 0 5 10 15 0 5 10 15 20 25 30 Flap angle 45 Axis air velocity 45 Flap angle 60 Axis air ve...

Страница 27: ... temp 80 F 26 7 C Fan speed High Cooling Flap angle 0 Axis air velocity 0 Flap angle 30 Axis air velocity 30 Flap angle 45 Axis air velocity 45 Flap angle 60 Axis air velocity 60 Indoor Unit KHS1271 0 5 10 15 0 5 10 15 20 25 30 Flap angle 0 Axis air velocity 0 Flap angle 30 Axis air velocity 30 0 5 10 15 0 5 10 15 20 25 30 Flap angle 45 Axis air velocity 45 Flap angle 60 Axis air velocity 60 27 ...

Страница 28: ...mpressor Performance at 115V Single phase 60Hz Rating conditions Running amp A 0 45 Power input W 45 9 85 950 10 3 995 Indoor Unit KHS1271 Outdoor Unit CH1271 Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 115V Single phase 60Hz Rating conditions Running amp A 0 45 Power input W 45 10 45 1 045 Heating Cooling 10 9 1 090 Indoor Unit Outdoor Unit Complete Unit F...

Страница 29: ... CONTROLLER FM GRN YEL FAN MOTOR CAPACITOR FAN MOTOR 1 3 5 1 2 3 1 3 5 1 2 3 ROOM THERMISTOR BLK BLK BLK WHT RED BLK BLK 1 2 3 4 1 2 3 4 COIL THERMISTOR ION 3P WHT HA JEM A 1 2 3 1 2 3 1 2 3 1 2 3 4P WHT 1 2 4 BLK 3 BLK BLK RED WHT 1 2 3 4 1 2 3 4 ION ASSY ION TERMINAL 1 3 5 1 3 5 1 2 3 WHT BLK RED 1 3 1 3 BRN PNK RED WHT BLK RED YEL BRN PNK CONNECTOR 8FA2 5257 71600 0 6 2 Electric Wiring Diagrams...

Страница 30: ... 2 2 CRANKCASE HEATER FERRITE CORE TERMINAL PLATE GND TO INDOOR UNIT POWER RELAY 6 1 4 5 BLK WHT RED BLK BLK BLK WHT 1 2 3 4 5 6 7 RV FM GRN YEL 4WAY VALVE COIL FAN MOTOR 1 2 3 4 5 6 7 1 2 3 4 5 6 7 BLK BLK BLK BLK YEL YEL YEL BLK BLK BLU RED BLK BLK BLK WHT YEL BLU RED BLK BLK YEL WHT GRY RED ORG WHT OUT DOOR THERMISTOR OVERLOAD RELAY OLR COIL THERMISTOR COMPRESSOR THERMISTOR 7P CONNECTOR WHT MV ...

Страница 31: ...set to B Fig 14 3 Press and hold the remote controller ION button and 1 HR TIMER button Then press and hold the ACL reset button with a pointed object such as the tip of a pen After 5 seconds release ACL button first then release ION and 1 HR TIMER buttons oP 1 test run appears blinking in the remote controller clock display area 4 Each time the 1 HR TIMER button is pressed the display changes as ...

Страница 32: ...lways hold the cover to disconnect See illustration at left For the connector without the resin cover push the lock in the direction of 2 while pulling it off How to Connect In order to connect hold the resin cover of the connector and push it in Confirm the click sound for the inside lock Pull the cover upward When the cover is pulled upward the lock is released with the sequence of 1 and 2 7 2 D...

Страница 33: ...en the remote controller malfunctions has been lost or otherwise cannot be used The set temperature is 4 F 2 C below the detected room temperature in the case of cooling operation and 4 F 2 C above the room temperature in the case of heating operation The flap and fan speed settings are AUTO GREEN RED Lamp Off COOL HEAT STOP When AUTO mode is selected the microprocessor calculates the difference b...

Страница 34: ...ears on the remote controller The main unit display lamp also becomes dimmer COOL and DRY modes When the night setback mode is selected the air conditioner automatically raises the temperature setting 2 F 1 C when 30 minutes have passed after the selection was made and then another 2 F 1 C after another 30 minutes have passed regardless of the indoor temperature when night setback was selected Thi...

Страница 35: ... drops to below 36 F 2 C continuously for 2 minutes or longer the compressor stops Once the freeze condition is detected the air conditioner will work less than the maximum frequency until it is turned off Approx 127 53 At stability of operation At start of operation A High LL Stopped A B C B Indoor heat exchanger A Control start B Control end Set fan speed 77 25 86 30 Approx 104 40 a b c d a b c ...

Страница 36: ...nce Releasing of defrosting Outdoor fan ON 4 way valve ON Outdoor heating exchanger temp is over 68 F 20 C Defrosting operation lasts 12 minutes maximum 2 minutes after it is stopped compressor is ON 4 way valve is ON Outdoor fan is ON If the air conditioner is turned off during the defrosting cycle it will continue defrosting and turn itself off after defrosting is completed Compressor 1 minute a...

Страница 37: ...d trouble diagnostics PROCEDURE Step 1 Press and hold the remote controller ION button and 1 HR TIMER button Then press and hold the ACL reset button with a pointed object such as the tip of a pen After 5 seconds release ACL button first then release ION and 1 HR TIMER buttons oP 1 test run appears blinking in the remote controller clock display area Step 2 Next press the 1 HR TIMER button once to...

Страница 38: ...detection only for the humidity sensor 3 Indoor outdoor PCboard failure 1 Sensor open circuit or short circuit 2 Contact failure at connector or open circuit at terminal crimping location 3 Outdoor PCboard failure Outdoor PCboard failure 1 Mis wiring 2 AC power failure 3 Blown fuse 4 Power Relay failure 5 Indoor or outdoor PCboard failure 6 Outdoor Fan Motor failure 7 Reactor failure 8 High Pressu...

Страница 39: ... current mode is TEST run If there are no problems with the above then check the outdoor unit 1 The rated voltage must be present between inter unit wirings 1 and 2 Connect a 5 k ohm resistor between inter unit wirings 2 and 3 When the voltage at both ends is measured approximately 12 to 15V DC must be output and the multimeter pointer must bounce once every 8 seconds Or instead of measuring the v...

Страница 40: ...age B For terminal strip short circuit work or inter unit wiring removal turn off the power to avoid an electric shock Release the terminal strip short circuit after the completion of self diagnostics Do not perform the short circuit work between any other terminals except for specified ones on the specified terminal strip If such work is performed between the incorrect terminals the unit might be...

Страница 41: ...he operation button on the indoor unit 2 Perform the self diagnosis five seconds after the operation start 1 Turn off the power and wait until the power lamp LED of the outdoor unit controller is turned OFF 2 Remove the short circuit between the terminals 2 and 3 on the outdoor unit terminal strip 3 Disconnect the cable from the terminal 3 on the indoor unit terminal strip Fig 4 Short circuit betw...

Страница 42: ...ter the operation start 1 Turn off the power and wait until the power lamp LED of the outdoor unit controller is turned OFF 2 Disconnect the cable from the terminal 3 on the Outdoor unit terminal strip Fig 6 Defect in the inter unit cable 1 Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit 2 Perform the self diagnosis five seconds after...

Страница 43: ...seconds but then quickly stops when the outdoor unit operates There is trouble in the system that provides feedback of motor rotation speed from the motor to the outdoor unit controller Trouble symptom 4 Fan motor rotation speed does not change during outdoor unit operation Trouble symptom 5 Fan motor rotation speed varies excessively during outdoor unit operation Remedy for symptom 3 to 5 It is n...

Страница 44: ...distance from the noise source 1 Use shielded wires 2 Move unit away from the noise source Trouble Either of the following trouble may occur 1 The unit may stop suddenly during operation 2 Indicator lamps may flicker 2 Electromagnetic interference This refers to noise generated by high speed switching of the microcomputer and compressor This noise radiates through space and returns to the electric...

Страница 45: ...g 1 10 1 2 Indoor Unit Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw on the terminal plate Fig 2 Note that the ground line terminal should be skipped for the check 10 1 3 Outdoor Unit Clamp a metallic part of the unit with the lead clip of the insulation resistance tester and me...

Страница 46: ... Fig 6 Fuse 10 2 Checking Continuity of Fuse on PCB Ass y Remove the PCB Ass y from the electrical component box Then pull out the fuse from the PCB Ass y Fig 5 Check for continuity using a multimeter as shown in Fig 6 46 ...

Страница 47: ...use of a change in composition of the remaining refrigerant Therefore do not add new refrigerant Instead recover the remaining refrigerant with the refrigerant recovery unit Then after evacuation totally recharge the specified amount of refrigerant with the new refrigerant at its normal mixed composition state in liquid phase When refrigerant R410A is used the composition will differ depending on ...

Страница 48: ...n R410A refrigerant is exposed to fire Therefore be sure to provide ample ventilation during installation work Caution in case of R410A leak Check for possible leak points with the special leak detector for R410A If a leak occurs inside the room immediately provide thorough ventilation A D Flare tool for R410A A D Conventional flare tool R22 Spacer 11 2 Checklist before Servicing Use a clutch type...

Страница 49: ...s which can be com monly used for R22 R407C and R410A CAUTION The above tools specifically for R410A must not be used for R22 and R407C Doing so will cause malfunction of the unit For the above vacuum pump 1 2 and vacuum pump adapter 3 those for R22 type units can be used for R410A type However they must be used exclusively for R410A and never alternately with R22 and R407C For details on tubing i...

Страница 50: ...it quickly 3 Checking for sealing Use nitrogen gas for the pressurized gas and never use a refrigerant other than R410A Also do not use oxygen or any flammable gas 4 Evacuation Use a solenoid valve installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption the valve will prevent the pump oil from flowing back The equipment may be damaged i...

Страница 51: ...use an electronic scale for charging refrigerant In this case if the volume of refrigerant in the cylinder becomes less than 20 of the fully charged amount the composition of the refrigerant starts to change Thus do not use the refrigerant if the amount in the charging cylinder is less than 20 Also charge the minimum necessary amount to the charging cylinder before using it to charge the air condi...

Страница 52: ...lux and wax for R410A Prevent oxide film from forming inside the tubes utilizing substitution with nitrogen N2 in the refrigerant circuit of the unit Leave ends of tubes open during welding 4 Checking for sealing Use nitrogen gas for the pressurized gas and never use a refrigerant other than R410A Also do not use oxygen or any flammable gas 5 Evacuation Use a solenoid valve installed vacuum pump s...

Страница 53: ... R410A for existing units which use R22 This will cause the air conditioner to operate improperly and may result in a hazardous condition 11 8 2 Use of Existing Tubing If replacing an older unit that used refrigerant R22 with a R410A unit do not use its existing tubing Instead completely new tubing must be used CAUTION Never charge additional refrigerant if refrigerant is leaking from the unit Fol...

Страница 54: ...INSTRUCTION MANUAL KHS0971 CH0971 KHS1271 CH1271 OI 852 6 4180 802 00 2 APPENDIX A A 1 ...

Страница 55: ...rner Auto Flap Control This automatically sets the flap to the optimum position during heating cooling and drying operation Automatic Switching between Cooling and Heating This unit automatically switches between cooling operation and heating operation according to the difference between the room temperature and the temperature setting Hot Start Heating System Right from the start the air is warm ...

Страница 56: ...e 25 Product Information If you have problems or questions concerning your Air Conditioner you will need the following information Model and serial numbers are on the nameplate on the bottom of the cabinet Model No ______________________ Serial No _______________________ Date of purchase ___________________________________________________ Dealer s address __________________________________________...

Страница 57: ... install this air conditioner where there are fumes or flammable gases or in an extremely humid space such as a greenhouse Do not install the air conditioner where excessively high heat generating objects are placed Avoid To protect the air conditioner from heavy corrosion avoid installing the outdoor unit where salty sea water can splash directly onto it or in sulphurous air near a spa Never use ...

Страница 58: ...lown out of the air conditioner through the air outlet Remote Control Unit The wireless remote control unit controls power ON OFF operation mode selection temperature fan speed timer setting and air sweeping Refrigerant Tubes The indoor and outdoor units are connected by copper tubes through which refrigerant gas flows Drain Hose Moisture in the room condenses and drains off through this hose Outd...

Страница 59: ...mp lights up red and orange alternately when the system is defrosting TIMER lamp This lamp lights when the system is being controlled by the timer QUIET lamp This lamp lights during operation in the QUIET mode ION lamp This lamp lights during operation in the ION mode while the indoor unit is operating The unit s display lamps are dimmed during operation in the NIGHT SETBACK mode QUIET REMOTE CONT...

Страница 60: ...mer OFF Timer 1 hour OFF Timer 5 NIGHT SETBACK 6 Confirmation of transmission 7 Auto flap indication Flap angle indication Sweep indication 8 High power operation 9 Quiet operation 10 ION operation Displayed when setting timer Displayed when transmitting data Displayed when indoor unit sensor is in use Displayed when setting temperature Displayed when temperature is shown Displayed when the time d...

Страница 61: ...negative ions generated during operation on and off ON OFF operation button This button is for turning the air conditioner on and off 1 HR TIMER button 1 HOUR OFF TIMER When you press this button regardless of whether the unit is operating or stopping the unit operates for one hour and then shuts down Transmitter Sensor Cover closed Display FAN SPEED selector button FLAP button ON TIME setting but...

Страница 62: ...e to save energy FLAP button Press this button either to select the setting of the airflow direction to the auto flap in each mode or one of the six possible positions manually or to select the sweep function which moves the flap up and down automatically Auto flap setting If selected in a heating operation the flap is set to position 3 in the following chart If selected in a cooling or dry operat...

Страница 63: ... not be bent The remote control unit sends the temperature signal to the air conditioner regularly at five minute intervals If the signal from the remote control unit stops for more than 15 minutes due to the loss of the remote control unit or other trouble the air conditioner will switch to the temperature sensor which is built into the indoor unit and control the room temperature In these cases ...

Страница 64: ...e remote control unit every 5 minutes Mounting the Remote Control Unit Before mounting the remote control unit press the ON OFF operation button at the mounting location to make sure that the air conditioner operates from that location The indoor unit should make a beeping sound to indicate that it has received the signal To take out the remote control unit pull it forward When Holding the Remote ...

Страница 65: ... selected and the unit is preset by following the steps below you can have the air conditioner automatically bring the room to the desired temperature simply by pressing the ON OFF operation button STEP 1 Press the MODE selector button to STEP 2 Press the ON OFF operation button To stop the air conditioner press the ON OFF operation button again To change the temperature setting press the temperat...

Страница 66: ...ration For cooling operation For fan only operation STEP 2 To start the air conditioner press the ON OFF operation button STEP 3 Press the TEMP setting buttons to change the temperature setting to the desired temperature Adjustable temperature range STEP 4 Set the FAN SPEED selector button to the setting you want STEP 5 Press the FLAP button and set the airflow direction as desired Refer to Adjust...

Страница 67: ...the event of power failure the unit will stop 3 Adjusting the Fan Speed A Automatic fan speed Simply set the FAN SPEED selector button to the position This automatically sets the best fan speed for the room temperature B Manual fan speed If you want to adjust fan speed manually during operation just set the FAN SPEED selector button as desired or 4 Fan Only If you want to circulate air without any...

Страница 68: ... of the indoor temperature when night setback was selected This enables you to save energy without sacrificing comfort This function is convenient when gentle cooling is needed Setting temperature Press the NIGHT SETBACK button 30 min 30 min Time 2 F 2 F When the night setback mode is selected the air conditioner automatically lowers the temperature setting 4 F when 30 minutes have passed after th...

Страница 69: ...essed the unit operates at maximum output for 30 minutes regardless of the desired temperature The fan speed is 1 step above High HIGH POWER Mode cannot be used when the operation mode is Automatic Operation QUIET Mode and HIGH POWER Mode cannot be used at the same time 8 ION Mode The ION mode is used during operation to generate negative ions that freshen up the air in the room Press the ION butt...

Страница 70: ...vary slightly depending upon the outdoor temperature and the way in which frost forms Cold draft prevention For several minutes after the start of heating operation the indoor fan runs at lower speed until the indoor heat exchanger coil has warmed up sufficiently However the fan may remain stopped when the room temperature is low This is because the COLD DRAFT PREVENTION SYSTEM is operating Someti...

Страница 71: ...Return button until PM 10 30 is displayed The time can be set in 1 minute increments Holding down the button advances the time rapidly in 10 minute increments 3 Press the CLOCK button again This completes the setting of the current time 1 Press the OFF TIME setting button once The timer indication is displayed and the present OFF time is shown 2 Press the Advance Return button until AM 11 00 is di...

Страница 72: ...r operates as if it is turned off Operation Indication 1 Press the ON TIME setting button once The timer indication is displayed and the present ON time is shown 2 Press the Advance Return button until AM 7 10 is displayed The timer indication blinks The time can be set in 10 minute increments Holding down the button advances the time rapidly in 10 minute increments 3 Wait a few seconds and then t...

Страница 73: ...to operate for one hour from that point in time and then stops It is not possible to use the OFF Timer and 1 Hour OFF Timer together Whichever function is set last takes precedence If the 1 HR TIMER button is pressed while the TIMER OFF function operates the OFF Timer is cancelled and the unit will stop operating one hour later 2 Operation together with the DAILY ON OFF REPEAT Timer The 1 Hour OFF...

Страница 74: ...on position until the air being blown out of the unit begins to warm Once the air warms up the flap position and fan speed change to the settings specified with the remote control Use the FLAP button on the remote control to adjust the position of the flap If you move the flap by hand the flap position according to the remote control and the actual flap position may no longer match If this should ...

Страница 75: ... 2 Do not pour water on the indoor unit to clean it This will damage the internal components and cause an electric shock hazard Casing and Grille Indoor Unit Clean the casing and grille of the indoor unit with a vacuum cleaner brush or wipe them with a clean soft cloth If these parts are stained use a clean cloth moistened with a mild liquid detergent When cleaning the grille be careful not to for...

Страница 76: ...y it How to replace the anti mold filter 1 With the FRONT mark of the anti mold filter at the front align the two indentions near the mark with the hooks at the rear of the air intake grille and then mount the anti mold filter 2 Allow the edge of the air intake grille to slide into the top of the indoor unit and then insert it all the way inside 3 Press in the bottom right and left corners of the ...

Страница 77: ...e stubborn dirt moisten a cloth in warm water no hotter than 104 F wring thoroughly and then wipe The air intake grille can be removed in order to wash it with water Removing and remounting the air intake grille Refer to How to remove the anti mold filter and How to replace the anti mold filter on page 23 When using a footstool or the like be careful not to let it tip over Washing the grille with ...

Страница 78: ... people in room 2 Eliminate heat source if possible 3 Doors and or windows are open 3 Shut them to keep the heat or cold out 4 Obstacle near air intake or air discharge port 4 Remove it to ensure good airflow 5 Thermostat is set too high for cooling or too low for heating 5 Set the temperature lower or higher 6 Outdoor temperature is too low for heating 6 Consult your dealer or try to use another ...

Страница 79: ...INSTALLATION INSTRUCTIONS KHS0971 CH0971 KHS1271 CH1271 II 852 6 4189 990 00 5 APPENDIX B A 2 ...

Страница 80: ...Inter unit Connections 3 9 Mounting 3 10 Drain Hose 4 HOW TO INSTALL THE OUTDOOR UNIT 16 4 1 Wiring Instructions for the Outdoor Unit 5 REFRIGERANT TUBING 17 5 1 Use of the Flaring Method 5 2 Flaring Procedure with a Flare Tool 5 3 Caution before Connecting Tubes Tightly 5 4 Connecting Tubing between Indoor and Outdoor Units 5 5 Insulation of Refrigerant Tubing 5 6 Taping the Tubes 5 7 Finishing t...

Страница 81: ...orting Be careful when picking up and moving the indoor and out door units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin alu minum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or meta...

Страница 82: ...hase these materials separately from a local source you will need 1 Deoxidized annealed copper tube for refrigerant tub ing as detailed in Table 2 Cut each tube to the appropriate lengths 1 to 1 4 30 cm to 40 cm to dampen vibration between units Table 2 2 Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing Wall thickness of the insulation should be...

Страница 83: ...nit more than 3 3 1 m away from any antenna or power lines or connecting wires used for television radio telephone security system or intercom Electrical noise from any of these sources may affect operation Drain hose Indoor unit Outside drainage Fig 1 2 5 cm min 6 15 cm min Front View 2 5 cm min Fig 2 INDOOR UNIT Tubing length L OUTDOOR UNIT Elevation difference H Fig 3a WARNING To prevent abnorm...

Страница 84: ...ife Figs 5b and 5c G Install cushion rubber under unit s feet to reduce vibration and noise Fig 5d G use lug bolts or equal to bolt down unit reducing vibration and noise G Install in a location where no antenna of a television or radio exists within 10 3 m Outdoor unit Hot air Heat source Exhaust fan NO Fig 4 Fig 5c Air intake Min 2 5 cm Air discharge Min 2 5 cm Min 8 20 cm Valve side Min 10 25 c...

Страница 85: ...ose and drain cap on page 14 3 2 Make a Hole 1 Place the rear panel from the indoor unit on the wall at the location selected Make sure the panel is hori zontal using a carpenter s level or tape measure to measure down from the ceiling Wait until after cut ting the hole before attaching the rear panel to the wall 2 Determine which side of the unit you should make the hole for tubing and wiring Fig...

Страница 86: ...is strong enough to sus pend the unit See either Item a or b below depending on the wall type a If Wooden Wall 1 Attach the rear panel to the wall with the 8 screws provided Fig 13 If you are not able to line up the holes in the rear panel with the beam locations marked on the wall use rawl plugs or toggle bolts to go through the holes on the panel or drill 3 16 5 mm dia holes in the panel over th...

Страница 87: ... part of the grille back into position 2 Make sure that the grille and frame are firmly fitted together by engaging the tabs 3 Attach the thermistor on the grille Fig 17a 4 Close the cover and replace the screw Fig 17a 5 Affix the grille with the 2 previously removed screws Fig 16b 6 Install the air intake grille a Allow the edge of the air intake grille to slide into the top of the indoor unit an...

Страница 88: ...gram 2 Provide a power outlet to be used exclusively for each unit with a power supply disconnect and cir cuit breaker for overcurrent protection provided in the exclusive line 3 To prevent possible hazards due to insulation fail ure the unit must be grounded 4 Each wiring connection must be done tightly and in accordance with the wiring system diagram Wrong wiring may cause the unit to misoperate...

Страница 89: ...onnected G No wire should be allowed to touch refrigerant tubing the compressor or any moving part Disconnect switch 1 2 3 1 2 3 4 5 6 Grounding line 115V 115V 115V INDOOR UNIT OUTDOOR UNIT Field supply Grounding line L N Power supply Single phase 115V 60HZ Terminal Terminal A B C B CAUTION G Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram The indoor uni...

Страница 90: ...Route the inter unit wiring from the back of the indoor unit and pull it toward the front for connec tion Fig 26a 26b 5 Connect the inter unit wiring to the corresponding terminals on the terminal plate Fig 26a 26b while referring to the wiring diagram 6 Be sure to secure the wiring with the provided clamp When closing the air intake grille press on both corners Fig 27 Please refer to How to repla...

Страница 91: ... the terminal screw 4 Shape the loop wire properly place it on the termi nal plate and fix it securely with the removed termi nal screw using a screwdriver I For stranded wiring 1 Cut the wire end with a cutting pliers then strip the insulation to expose the stranded wiring about 3 8 10 mm and tightly twist the wire ends Figs 30 and 31 2 Using a screwdriver remove the terminal screw s on the termi...

Страница 92: ...the wall Adjust the indoor unit so it is securely seated on the rear panel Fig 36 3 Carefully bend the tubing if necessary to run along the wall in the direction of the outdoor unit and then tape as far as the fittings See Caution on page 18 The drain hose should come straight down the wall to a point where water runoff won t stain the wall 4 Connect the refrigerant tubing to the outdoor unit Afte...

Страница 93: ...the drain hose fully onto the drain pan outlet until the drain hose edge is pushed into the insula tion Check that the screw holes in the drain bracket and the drain pan outlet are aligned and securely in contact then fasten them with the screw After attaching the drain hose check that it is attached securely Fig 40c Drain cap Use a Phillips screwdriver to push the drain cap in firmly If it is dif...

Страница 94: ...f the hose c If the drain hose will run in the room insulate the hose with insulation so that chilled condensation will not damage furniture or floors Fig 44 Foamed polyethylene or its equivalent is recom mended WARNING Risk of Electric Shock Do not supply power to the unit or operate it until all tubing and wiring to the out side unit are completed Condensation Insulation material Locally purchas...

Страница 95: ...s 1 Remove access panel C Fig 46 2 Connect the inter unit and power supply line accord ing to the drawing on the panel side 3 Be sure to size each wire allowing approx 4 10 cm longer than the required length for wiring Store excess wiring inside the cabinet 4 When connections are completed check that all connections are correct as shown in the wiring sys tem diagram on panel side 5 Be sure to grou...

Страница 96: ...ool Figs 49a and 49b Use RIGID or equivalent A good flare should have the following characteristics G inside surface is glossy and smooth G edge is smooth G tapered sides are of uniform length 5 3 Caution before Connecting Tubes Tightly a Be sure to apply a sealing cap or water proof tape to prevent dust or water from getting into the tubes before they are used b Be sure to apply refrigerant lubri...

Страница 97: ...half of each previous tape turn Fig 55 3 Clamp the tubing bundle to wall using 1 clamp approx every 47 120 cm Do not wind the armoring tape too tightly since this will decrease the heat insulation effect Also be sure the con densation drain hose splits away from the bundle and drips clear of the unit and the tubing 5 7 Finishing the Installation After finishing insulating and taping over the tubin...

Страница 98: ... time for evacuation Table 7 Hi Lo Indoor unit Outdoor unit Manifold valve Exclusively for R410A Pressure gauge Vacuum pump Charging hose Exclusively for R410A Vacuum pump adapter Exclusively for R410A with reverse flow prevention Fig 57 CAUTION Be sure to use a manifold valve for air purging If it is not avail able use a stop valve field sup ply for this purpose The Hi knob of the manifold valve ...

Страница 99: ...rt slightly to release the pressure Then remove the hose 11 Fasten the valve cap on the wide tube service port securely with an adjustable wrench or box wrench Next mount the valve cap on the service valve and tighten it to 170 lbs in 200 kgf cm with a torque wrench This process is very important to prevent gas from leaking from the system 12 Test run the air conditioner See next page 13 While the...

Страница 100: ...ain unit blinking Fig 59c After 3 minutes the system shifts into cooling opera tion and cool air will start to be felt Cool mode test run is unaffected by the room temperature 3 Press the ON OFF operation button of the remote con troller again to stop the test run Fig 59a 4 Finally press the ACL reset button of the remote con troller to release it from Test Run mode to return to nor mal mode Fig 5...

Страница 101: ...ube valve stem Then quickly stop the unit 5 Disconnect all gauges and hoses and replace the valve caps as they were before I Basic Functions of the Service Valves The basic functions of the service valves are given in Table 8 below Action Narrow Tube Service Valve 2 Way Wide Tube Service Valve 3 Way CLOSED Fully OPEN Fully OPEN Shipping Operating and test running the air conditioner Measuring pres...

Страница 102: ...there is an obstacle between the remote con trol unit and the air conditioner since a check signal is sent from the remote control unit every 5 minutes 7 1 Mounting on a Wall Before mounting the remote control unit press the ON OFF operation button at the mounting location to make sure that the air conditioner operates from that location The indoor unit should make a beeping sound to indicate that...

Страница 103: ...in object such as the tip of a pen to press the ACL button When this has been done oP 1 test run appears blinking in the remote controller clock display area 4 Each time the 1 HR TIMER button is pressed the display changes as shown below Press this button 2 times to change the display to oP 7 address setting Fig 64 5 oP 7 has now been selected for address setting 6 Press the ON OFF operation butto...

Страница 104: ...YO Commercial Solutions A Division of SANYO North America Corporation 1300 Michael Drive Suite A Wood Dale IL 60191 U S A Sanyo Canada Inc 1 300 Applewood Crescent Concord Ontario L4K 5C7 CANADA Apr 2009 T ...