8. INSTALLATION INSTRUCTIONS
Table 3
Max. Allowable Tubing
Limit of Tubing
Limit of Elevation
Required Amount of
Model
Length at Shipment
Length (L)
Difference (H)
Additional Refrigerant
(ft.)
(ft.)
(ft.)
(oz./ft.)*
C2462R, CL2462R
23
132
50
0.43
* If total tubing length becomes 23 to 132 ft. (max.), additional refrigerant (R410A) charge of 0.43 oz./ft. is required.
No additional charge of compressor oil is necessary.
1)
Tubing Length
• Refrigerant tubing between the indoor and
outdoor units should be kept as short as
possible.
• Select and decide the installation location
so that the length of the refrigerant tubing
will be within the limits given in Table 1.
Fig. 1
Tubing length (L)
INDOOR
UNIT
OUTDOOR
UNIT
Elevation difference (H)
0711_M_I