  Push the front 

cover until the claw 

hook to the left side.

 

 

For service personnel only 

⑨  ⑪ 

Slide the switch 

to

Inverter

」.

 

I

nsert  the tabs  into  the slots  and 

slide it to the right until you hear a 

click  sound.  Secure  it  with  the 

screws.

 

If the

 Forced Bypass

   

is on   

Bypass

  side, set it to 

Inverter

  side

 

If the UPS is in operation, the

INV.ON/STAND BY 

green

  is blinking

Press 

  for 1 second and 

check if

INV.ON/STAND BY green

turns on, then 

proceed to step

  ⑫.

 

Caution 

For service personnel only 

⑨  ⑪ 

Slide the switch

 

to

Inverter

」.

 

 

Insert the tabs into the slots and slide it down until 

you hear a click sound. Secure it with the screws. 

 

Attach and slide the front 

cover in the direction of the 

arrow until the claw hook. 

 

 

Attach and slide the front 

covers in the direction of the 

arrow until the claw hook.

 

 

Insert the tabs into the slots and slide it down until 

you hear a click sound. Secure it with the screws.

 

For service personnel only 

⑨  ⑪ 

Slide the switch 

to

Inverter

」.

 

Содержание A11H Series

Страница 1: ... in the table above is always occuring on the battery terminal so do not touch them with your hands or short circuit them There is a risk of electrick shock or injury Also for safety use insulation method such as attaching vinyl tape to the used battery pack connector To safely replace the battery pack please refer to the A11H insturction manual M0011840 B Ba at tt te er ry y R Re ep pl la ac ce e...

Страница 2: ...ed that you do it in a short period of time because you will not be able to back up when an input abnormality such as a power outage occurs during replacement A11H stop For more information on stopping procedures please refer to A11H s Instruction Manual Stop the load equipment If the A11H U model is used as a UL Standard Product and CE Marking Conformity Product you may not be able to replace the...

Страница 3: ...ge and charging of the battery Battery disintergrate during storage so please use as soon as possible Store the battery in a dry place where the temperature is low During storage please charge once at least every 6 months storage temperature 25 and before use Please charge with the UPS charger Refer to A11H Owner s Manual Charging the UPS 3 Battery Transportation and Handling As a rule avoid abnor...

Страница 4: ...o be careful no to pinch your hands when dealing with battery packs The A11H302 battery pack has a scale at the top shown on page 1 When the scale is seen keep the bottom part supported with both hands and be careful not to drop it Remove by sliding in the direction of the arrow by holding two places of strongly Battery Cover Loosen the screw and slide the battery cover in the direction of the arr...

Страница 5: ...ome off the battery cover For service personnel only Slide the switch to Bypass Pull out the battery pack out Disconnect the battery conn ector Attach the tape and insulate it For service personnel only Slide the switch to Bypass Disconnect the battery connector Attach the tape and insulate it Pull out the battery pack out Remove by sliding in the direction of the arrow by holding two places of st...

Страница 6: ...y pack depends on the model Please see the size on page 1 If you have an additional battery module replace the battery after Insert the battery pack in the direction of the arrow Plug in the battery connector until you hear a click sound Plug in the battery connector until you hear a click sound The diagram shows the case of A11H202 The size of the battery pack depends on the model Please see the ...

Страница 7: ... switch Forced Bypass is on the Inverter side the LED OUTPUT green and INV ON STAND BY green on the front panel are lit when the UPS is in operation Install the battery cover Fit the front cover When it is not used as a UL Standard When it is used as a UL Standard for service personnel When it is used as a UL Standard and CE Marking Conformity Product for service personnel ...

Страница 8: ...is blinking Press for 1 second and check if INV ON STAND BY green turns on then proceed to step Caution For service personnel only Slide the switch to Inverter Insert the tabs into the slots and slide it down until you hear a click sound Secure it with the screws Attach and slide the front cover in the direction of the arrow until the claw hook Attach and slide the front covers in the direction of...

Страница 9: ... the battery information after replacing the battery If you do this incorrectly the battery life warning will not display correctly The MAIN SW on the back side is set to ON 1 INV ON STAND BY green and OUTPUT green are not blinking 2 UPS is in user setting mode Buzzer beep beep Either BATT LOW or 25 is blinking or both INPUT Blinking Off Blinking Indicator 1 can be operated either ON or OFF state ...

Страница 10: ...o normal operation After resetting the setting are automatically returned to Do not reset ress for 3 4 seconds and release it when the buzzer alarms If BATT LOW is still blinking the battery information is not reset correctly Please reset it again Caution Press 3 4 seconds and release it when the buzzer rings beep beep ...

Страница 11: ...d on January 2015 the next replacement period is after four years and 6 months from the date of replacement 2019year 6month JUN 2019 Caution for Storage Battery replacement Label If the second row is already filled in write the replacement date in a memo and attached it in a visible place that is easy to see but will not be a hindrance to UPS intake exhaust fan 2019 JUN Please fill in with marker ...

Страница 12: ...ent date using an indelible pen such as a permanent marker Average Ambient Operating Temperature Expected Battery Lifetime Battery Replacement Period 25 77 F 5 years 4 5 years 30 86 F 3 5 years 3 years 35 95 F 2 5 years 2 years 40 104 F 1 7 years 1 5 years Note The temperature may greatly affect the service life of the battery as shown in the table above To secure safe operation always replace the...

Отзывы: