4
1-5. Additional Materials Required for Installation
1.
Refrigeration (armored) tape
2.
Insulated staples or clamps for connecting wire
(See local codes)
3.
Putty
4.
Refrigeration lubricant
5.
Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
AVOID:
G
direct sunlight.
G
nearby heat sources that may affect performance of the unit.
G
areas where leakage of flammable gas may be expected.
G
places where large amounts of oil mist exist.
DO:
G
select an appropriate position from which every corner of
the room can be uniformly cooled. (High on a wall is best.)
G
select a location that will hold the weight of the unit.
G
select a location where tubing and drain hose have the
shortest run to the outside. (Fig. 1)
G
allow room for operation and maintenance as well as unre-
stricted air flow around the unit. (Fig. 2)
G
install the unit within the maximum elevation difference (H)
above or below the outdoor unit and within a total tubing length
(L) from the outdoor unit as detailed in Table 3 and Fig. 3a.
G
Install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for television,
radio, telephone, security system, or intercom. Electrical noise
from any of these sources may affect operation.
Drai
n
ho
s
e
I
n
door
un
it
O
u
t
s
ide drai
n
a
g
e
Fig. 1
2" (5 cm)
min.
6" (15 cm)
min.
Front View
2" (5 cm)
min.
Fig. 2
INDOOR
UNIT
T
u
bi
ng
le
ng
th (L)
OUTDOOR
UNIT
Elevatio
n
differe
n
ce (H)
Fig. 3a
WARNING
To prevent abnormal heat genera-
tion and the possibility of fire, do
not place obstacles, enclosures
and grilles in front of or surround-
ing the air conditioner in a way
that may block air flow.
*
If total tubing length becomes 25 to 98 ft. (Max.) or 33 to 98 ft. (Max.), charge additional refrigerant (R410A) by 0.27 oz./ft.
No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.
Indoor unit
Floor level
Wall
Minimum height
from floor level
5' (1.5 m)
Fig. 3b
For stable operation of the
air conditioner, do not
install wall-mounted type
indoor units less than 5'
(1.5 m) from floor level.
CAUTION
Max. Allowable Tubing
Limit of Tubing
Limit of Elevation
Required Amount of
Model
Length at Shipment
Length (L)
Difference (H)
Additional Refrigerant
(ft.)
(ft.)
(ft.)
(oz./ft.)
*
KHS1872
25
98
49
0.27
KHS2472
33
98
49
0.27
Table 3
07-153 CH1872-2472 6/12/07 3:15 PM Page 4
Содержание 200 BTU
Страница 15: ...3 DIMENSIONAL DATA Indoor Unit KHS1872 KHS2472 Unit inch mm 15 ...
Страница 61: ...INSTRUCTION MANUAL KHS1872 CH1872 KHS2472 CH2472 OI 852 6 4180 801 00 2 APPENDIX A A 1 ...
Страница 86: ...INSTALLATION INSTRUCTIONS KHS1872 CH1872 KHS2472 CH2472 II 852 6 4189 989 00 3 APPENDIX B A 2 ...