SANUVOX 24V UV LAMP SYSTEM 
INSTALLATION INSTRUCTIONS

 www.sanuvox.com

1.

Disconnect power to the HVAC unit.

2.

Remove the ballast, brackets, UV lamp retaining ring, view port, and UV lamp from the package.

3.

Locate the ballast so that there is sufficient cable to attach to the UV lamp when it is installed.

4.

The two piece lamp bracket is used to hold the lamp. Depending on the type of coil and the location of the UV light on the coil will determine if one or both

pieces of the bracket are used. The UV lamp will be installed either with the lamp on top of the coil or the lamp inside the coil.

5.

The main bracket can be mounted to the side of the coil allowing the UV lamp to be inserted in-between or over the coil. Drill a 1” diameter hole in the sheet

metal to allow the UV lamp to pass and mount the main bracket to the side of the coil using the two included sheet metal screws. Once installed use the

round metal lamp retaining ring to lock the lamp in place and tighten the two screws.

Use of magnetic multi-bracket: 

The magnetic multi-bracket allows for various lamp installations. Inspect the ideal location for the UV lamp system

and use the main bracket and magnetic multi-bracket together if desired.

6.

Connect the plug onto the lamp pins. The plug is designed so that it can only be installed one way. You may have to rotate the socket 90 degrees to line up

the pins with the holes.

7.

Drill a ¼ inch hole on the outside of the plenum on one side of the coil and install the view port. When the UV lamp is operational, the glow of the lamp will be

visible through this port.

8.

Connect the black and white wires to the 24VAC terminals on the HVAC equipment. Make sure that the HVAC equipment can at least supply 20VA. If not we

recommend the use of a dedicated transformer that provides 24VAC with a minimum of 20VA otherwise it will not be sufficient to power the ballast and lamp.

9.

Reconnect power to the HVAC unit or plug in the transformer in a power outlet.

Ballast Operation, LED Notification & Reset

The 24V ballast is equipped with an LED status notifying the user of various system conditions. The LED notifications work as follows:

RESET BUTTON: To reset an error code, press RESET button once. Following a lamp replacement, press 

and hold 

the RESET button for 3 seconds to reset the 1 

year timing function.

Maintenance

Disconnect all power before performing any maintenance or service. The UV lamp should be cleaned every two to three months. To clean, disconnect white socket 

from lamp. Loosen the 2 screws on the retainer ring. Turn retainer ring left. Pull out retainer ring and pull lamp out. Wipe lamp with a soft tissue and alcohol based 

solution. Reverse the above procedure to reinstall the lamp. Lamp need

s

 periodic replacement to maintain design specifications. Replace lamp after 1 year of 

operation. Follow instructions for ballast operation (above) on how to reset the timer feature. Contact a local dealer for replacement lamps.

Warranty

UV Lamp, 1 year warranty. Ballast, 5 years warranty. 

Example 1

Over the coil

(parallel or perpendicular)

Example 2

Inside the coil

Sample Installations

Insert UV lamp into bracket and place 

UV lamp retaining ring, lock into place 

and tighten both screws.

16" UVC lamp

Magnetic 

multi-

bracket

Evaporator Coil

CAUTION: UV exposure is dangerous to eyes, skin 

Lamp 

retaining 

ring

System OK

LED Solid

Lamp > 8,700 hrs. (time to replace UV Lamp)

 

LED FLASH 1 sec. / 

pause 

1 sec. Repeat.

Lamp Fail

LED FLASH 2X / pause 1 sec. Repeat.

Ballast Fail

LED FLASH 3X / pause 1 sec. Repeat.

Low Voltage (under 18V)*

 

LED FLASH 4X / pause 1 sec. Repeat.

High Voltage (over 30V)*

LED FLASH 5X / pause 1 sec. Repeat.

*

Connect w/ step-down transformer. Sold separately.

1-888-726-8869

REPLACEMENTS PARTS

Lamp :  
Ballast : 

     LMPRGPT160T5

 

 

 

BST24G48ET

Transformer :    MSCTFR12024    

120 - 24 V