3.2 PLUMBING
3.2.1 Refer to the section IMPORTANT INSTALLATION POINTS. Plumb in the
valves in the sequence shown in Figure 03. Ensure the valves are installed in
the correct orientation by reference to the direction of flow arrows marked
on them. The Expansion Vessel should be supported by its own wall bracket
(supplied), do not rely on the pipework alone to support it.
3.2.2 The water connections to the unit are 15mm diameter copper tubes suitable
for compression fittings. Do not use solder joints as this will damage the
heater and may prevent servicing under warranty.
3.2.3 The INLET is marked BLUE, the OUTLET is marked RED. Several
hot outlets via conventional taps can be served, however, individual site
demands should be considered when choosing capacity and the number of
outlets to be served.
3.2.4 It is recommended that a WRAS Listed isolating valve is fitted on the cold
water supply to the heater.
3.2.5 A drain cock must be fitted below the heater in the inlet pipework. It must
be sited between the heater and the Check Valve (see Figure 03).
3.2.6 Plumbers Paste must not be used as it can impair the operation of the valves.