background image

GB9221 series instruction manual

-1-

emergency broadcast at fire or other accident scenes.In the field of fire broadcast,

GB9221 must be used with the GB9242(Fire Broadcasting Host)to complete the fire

broadcast. Background music broadcast can be directly played by external input source

signals (such as CD/MP3 player, tuner, etc.) when there’s no accident event.

2) The display of GB9221 series fire alarm broadcast amplifiers is built-in LED

indicator lights.These built-in LED indicator lights can indicate various operating

conditions and fault conditions.All the functions can be set up with light touch

buttons.

3 ) GB9221 series fire alarm broadcast amplifiers only contain the power

amplification section of the GB9242(Fire Broadcasting Host). The output power could

be 150W/300W/500W.

4) GB9221 series fire alarm broadcast amplifiers assemble high quality power

transformers internally.The static power consumption is low and the overload

capability is high.GB9221 series have overload and over-temperature protection

circuit, buzzer alarm when a fault occurs.

2 Main Specifications

1) Power supply:

10%,-15%,50Hz)

DC:see table1-1

2) Line input sensitivity:

300mV ~775mV(line1、line2)

3) Line output level:

500mV ± 100mV

4) Effective frequency range

for distortion limitation: 80Hz ~ 8kHz

5) Total harmonic distortion:< 5%

6) SNR:

> 70dB

7) Monitor power:

3W

8) Fixed output voltage:

120V(fixed voltage mode)

9) Rated output power:

150W/300W/500W

10) Working environment:

a)temperature

0℃-40℃

b)humidity

<92%

11) Insulation resistance:

a)backup power input&the chassis

>20MΩ(DC500V)

b)AC input voltage&the chassis

>50MΩ(DC500V)

c)fixed output voltage&the chassis

>50MΩ(DC500V)

Содержание GB9221 Series

Страница 1: ...on manual before installation and use GB9221 series fire alarm broadcast amplifier Instruction manual suitable for 150W 300W 500W 2017 1 0 1 Overview 1 GB9221 series fire alarm broadcast amplifiers ar...

Страница 2: ...42 Fire Broadcasting Host The output power could be 150W 300W 500W 4 GB9221 series fire alarm broadcast amplifiers assemble high quality power transformers internally The static power consumption is l...

Страница 3: ...ower on off 2 volume adjustment LED indicator 3 volume adjustment knob 4 button self test 5 button silence 6 button monitor 7 over temperature fault LED indicator 8 overload fault LED indicator 9 outp...

Страница 4: ...ed cable Pay attention to the order of N L E b Connect the backup power supply that meets the nominal requirements to the Standby Power terminal Pay attention to positive and negative polarity c Power...

Страница 5: ...age machine when the power is turned on under short conditions 4 When the circuit debug finished preset volume should be set after the fire alarm is triggered After the preset volume is set the machin...

Страница 6: ...Over temperature Over temperature because running under heavy load Reduce the output power or use after the temperature drops Over voltage Over voltage because light load Reduce the output amplitude a...

Страница 7: ...48V 5A 15A GB9221 150W 150W 24V 3A 15A Table 1 1 Equipment model and parameter comparison table 11 Attached parts and components No Project Notes 1 Instruction manual 1 2 2 AC fuses 2 DC fuses See tab...