3

Fig.3

V. Installation

Definitions of terminals (non-polarity Two-wire system)

1->Loop terminal (L1/L2)

3->Loop terminal (L2/L1)

F

ig.4

Base and wiring diagram

1.

Use two M4 screws to fix the DZ-9091K base via the two elliptic screw holes(see Fig.4),then connect

the bus cables with the terminal 1&3, finally twist the main body onto the base.

2.

If the sounder Beacon is required to be tamper-proof, fix it with ST2.9×5 self-tapping screws thought

the tamper-proof hole (see Fig. 5)on the base.

Fig. 5

4

VI.

Sound Level Data(EN54-3 approved)

Tone1:[email protected],Max Volume,dB(A)@1m

Angle

Horizontal

Vertical

Voltage

20V

28V

20V

28V

15

°

81.2

84.9

81.0

84.6

45

°

77.0

80.0

75.0

78.0

75

°

83.8

86.9

83.0

86.6

105

°

83.5

86.6

83.0

85.7

135

°

77.4

80.1

75.3

78.7

165

°

80.7

83.2

79.2

82.9

Address: 3/F, Guangcai Xintiandi Mansion, Nanshan Road, Nanshan District, Shenzhen, Guangdong, 518054, P.R.China