Version number: 210200180326
respectively, and a 1N4007 diode should be in series between COM1 and COM2 then connected with
the controlled equipment. The details of the wiring method is shown in Fig. 3.
Fig 3. Wiring method of Voltage Output
V. Installation and debugging
1. Make sure the A9056T module matches the type given on the construction drawings.
2. Connect the 4-pin coding plug on the coder with the 4-pin coding socket (see Fig.1) on the main body
of the A9056T module and then set the coder with the coding function and compile the correct address
code to finish the address coding.
3. Conduct correct wiring as instructed in Fig.3 or Fig.4.
4. Use two M4 screws to fix the module base via the two elliptic screw holes shown in Fig.2 and then
insert the main body of the A9056T module into the module base and make sure they contact each other
well.
5. After the A9056T module is installed and checked, connect the power supply of the fire alarm control
system.Upon successful login, the inspection indicator of the A9056T module will blink once about every
12 seconds, which suggests that the A9056T module has begun to operate.
6. Conduct debugging after the installation is completed. Make the fire alarm control system send out a
starting signal and have the starting signal sent by the A9056T module to the fire linkage equipment
connected with it. After that, the fire linkage equipment will operate correspondingly and the inspection
indicator of the A9056T module will be lit. The operating fire linkage equipment will give a feedback
signal. After receiving the feedback signal, the A9056T module will have its input indicator lit, which
suggests that it has begun to operate normally.
7. After the debugging, reset the A9056T module and related equipment.
VI. Precautions
1. Do not connect the output to the AC singal, or the A056T module may be damaged.
2. For active output, NO1 should be connected with DC24 passive, and NO2 with DC24 negative.
3. Confirm the type of the input equipment connected with the A9056T module (feedback equipment or
fire alarm equipment) and have the corresponding equipment type of the A056T module set in the fire
alarm control panel. After automatic login, the A9056T module will treat the input equipment as fire alarm
equipment by default.
Address
:
3F, Guangcai Xintiandi Mansion, Nanshan Road, Nanshan District, Shenzhen, 518054, China
Tel
:
+86(755)86226969
Fax:
:
+86(755)86223939
L1
L1
L1
COM1
L1
COM1
L2
L2
47K
Ω
resister
L2
L2
47K
Ω
resister
COM2
COM2
TO+
+24V
TO+
NO1
47K
Ω
resister
NO1
47K
Ω
resister
GND
TO-
Normal closed input
Normal open input
NO2
TO-
NO2
+24V
D2
D1
D1
D2
GND
A9056T
A9056T