Installation & Operation 

 

3.1

 

System ON and OFF 

 

Turn the Fans On.  

 

Turn the key switch to ON position. 

 

To turn the system off, turn the key switch to OFF position.  

 

3.2

 

Emergency Shut Off  

The emergency shut off button is located on the front of the panel.  
There is also a facility for remote shut off buttons to be wired in series on the circuit board. 
 
The emergency shut off button(s) will cut off the gas supply when activated.  
To reinstate the system, the emergency shut off button(s) will need to be reset and the panel 
restarted.  

 

3.3

 

BMS integration 

The Merlin 1500S can be integrated with a BMS to make or break a circuit on 
gas on/gas off, (valve open or valve closed). This will tell the BMS whether or not 
power is being sent to the solenoid. 
 
There is a dip-switch located on the inside facia of the Merlin 1500S labelled 
[BMS SEL].  
 
This is factory set in the OFF position which signals the BMS on gas on/gas off.  
When switched to the ON position, the 1500S will only signal the BMS on a fault, i.e. 
fan fault, CO2 high level detected, gas detected, EM Stop pressed, etc.  
 

 

3.4

 

Fan Switch Integration  

There is the facility to connect a Fan Switch (FS1 or FS2 sold separately).  
The Fan Switch provides the facility to turn on the fan(s) when the key switch on the Merlin 1500S 
is in the on position and turn the power off to the fan(s) when the key switch on the Merlin 1500S 
is in the off position.  
 
There is a dip-switch located inside the facia of the Merlin 1500S labelled [EM SEL].  
 
This is factory set in the OFF position which instructs the system to shut down the fan(s) and gas 
supply on activation of the Emergency shut off button(s).  
 
On installation, this can be switched to the ON position if required. This will 
instruct the system to leave the fans on and only shut off the gas supply on 
activation of the Emergency shut off button(s).  
 
Note: This option is not available if Fan Switch is not installed.  

 

Содержание Merlin 1500S

Страница 1: ...Merlin 1500S User Guide Rev 07 05 19 1 Gas Safety Products Merlin 1500S Gas Ventilation Interlock system User Guide Please read this guide carefully and retain for future use...

Страница 2: ...FAN EXTRACT FAN PD SWITCHES 4 2 4 BMS OUT 4 2 5 EM REMOTE 4 2 6 GAS DETECTOR 5 2 7 FS 1 2 3 4 5 2 8 CO2 MONITOR 5 2 9 12V DC 5 3 Installation Operation 6 3 1 System ON and OFF 6 3 2 Emergency Shut Off...

Страница 3: ...should be removed before drilling entry holes into the case Important Warning Statements Never ignore your device when in alarm This device requires a continual supply of electrical power it will not...

Страница 4: ...connections If only one fan is being used the terminals not in use should be left linked out 2 4 BMS OUT Terminal connections are available on the circuit board for connections to Building Management...

Страница 5: ...arately which can provide power to the fans when the control panel is switched on 2 8 CO2 MONITOR This terminal can be wired to CO2 monitor to shut off the system in the event of CO2 being at alarm le...

Страница 6: ...SEL This is factory set in the OFF position which signals the BMS on gas on gas off When switched to the ON position the 1500S will only signal the BMS on a fault i e fan fault CO2 high level detected...

Страница 7: ...not illuminate Gas On When the fans are running at the correct speed and the key switch is turned on the Merlin 1500S will open the gas valve and the green Gas On LED will illuminate ON Gas On OFF Ga...

Страница 8: ...Under normal working conditions this LED is off If the external Merlin detector connected detects gas this will show RED and the Gas valve will turn off OFF OK ON Gas detected CO2 High Under normal wo...

Страница 9: ...l pressure differential switch or current switch VOLT FREE INPUT 9 BMS OUT contacts Normally Closed Common and Normally Open 10 PRESSURE SENSOR Disabled 11 EM REMOTE Remote EM Stop buttons and Fire Al...

Страница 10: ...Merlin 1500S User Guide Rev 07 05 19 10...

Страница 11: ...Merlin 1500S User Guide Rev 07 05 19 11...

Страница 12: ...liable for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the consumer or any other user of this product whether due to a...

Отзывы: