background image

Installation & Operation Manual                                                                                       Merlin GDP2 

 

 

Rev: 09   01-20

 

9  

OPERATION 

   First Power Up 

 

On connecting mains power, press reset to start the testing sequence. 
The system will close the solenoid valve when an emergency stop has been pressed, gas has   
been detected or any alarm signal has been triggered. 
 
When the system is connected to the mains power supply, the Power LED will illuminate RED.  
 

   LED Indicator Status 

 
Power 
When the system is connected to the mains power supply, the Power LED will illuminate RED.  
When no power is present, this LED will not light up.  
 
Gas On 
On start up the Gas on LED will flash for one minute to check for gas being detected.  
If no gas detected or any other faults the gas valve will open and the Gas On LED will 
illuminate.

  

GREEN = Gas On  
OFF = Gas Off 
If the test is unsuccessful the relevant zone LED light will illuminate to indicate a fault. 
 
EM Stop 
If an emergency shut off button (either remote or on the panel) is pressed, the LED will 
illuminate AMBER and the gas will be turned off.  
The EM Stop button must be re-set before restarting the system. 
OFF = OK  
AMBER = EM Stop button pressed 
 
Heat Detector 
 Under normal working conditions this LED is off. If the fusible link melts at 72 Degrees Celsius or 
higher, the LED will show AMBER and the Gas valve will turn off.  
 
Fire Alarm 
If the fire alarm panel has been activated, the LED will illuminate Amber and the gas will be 
turned off. The Fire alarm panel must be re-set before restarting the system. 
Off = OK 
AMBER = Fire alarm activated. 
 
Zones 1-2 
Under normal working conditions this LED is GREEN.  
If the gas detector connected reaches the low level alarm this will show AMBER.  
If the gas detector connected reaches high level alarm this will show RED and the gas solenoid 
valve will close if connected. 
 
 

Содержание Merlin GDP2

Страница 1: ...range of detection panels which can be used in many applications such as factories car parks shopping centres and most commonly boiler houses The GDP2 can be used with up to eight Merlin gas detector...

Страница 2: ...Wiring and Set Up Switch 6 Auto Reset Set Up Switch 7 Zone 1 Zone 2 Set Up Switch 7 Factory Set Condition 7 Trouble Shooting 7 Specification 8 OPERATION 9 First Power Up 9 LED Indicator Status 9 Mute...

Страница 3: ...nsors Generally the installation height of a sensor for a heavy gas such as propane would be close to the lowest point in the area and for a light gas such as methane would be close to the highest poi...

Страница 4: ...ly 5 Remote emergency stop buttons Volt free purchased separately 6 Heat Sensor Fusible Links Volt free purchased separately 7 Fire panel connection Volt free not included 8 BMS output contacts Normal...

Страница 5: ...from the GAS VALVE connector using a 3 core cable can be connected to a gas solenoid valve which can shut the gas supply on alarm status Refer to your valve manual for more information and wiring GAS...

Страница 6: ...connections for an external sounder alarm strobe lighting to activate on alarm Refer to your sounder strobe manual for wiring BMS Wiring and Set Up Switch Connections are available on the board for Bu...

Страница 7: ...tart when power is restored Zone 1 Zone 2 Set Up Switch There are dip switches located on the GDP2 circuit board labelled ZONE 1 ZONE 2 This is factory set in the Off position For each of the gas dete...

Страница 8: ...alve Output Voltage 100 240V AC Current Consumption 20W max full load Internal Fuse 3 15A Operating Temperature 0 40 C 0 95 RH Non Condensing Audible Alarm Buzzer dB 65 dB 300mm distance in quiet cond...

Страница 9: ...is unsuccessful the relevant zone LED light will illuminate to indicate a fault EM Stop If an emergency shut off button either remote or on the panel is pressed the LED will illuminate AMBER and the...

Страница 10: ...y by exposing it to the target gas A known concentration of the target gas is applied to the sensor to trigger an alarm condition and ascertain the detector is working safely Why is it important A det...

Страница 11: ...product will be free of defects in material and workmanship for a period of three 3 years from date of purchase The manufacturer s liability hereunder is limited to replacement of the product with rep...

Страница 12: ...on Location Organisation Stamp Signature of the installer Contact Us S S Northern Head Office Tel 44 0 1257 470 983 Fax 44 0 1257 471 937 www snsnorthern com info snsnorthern com South East Division T...

Отзывы: