S&S Northern Merlin CT1250 Скачать руководство пользователя страница 7

Merlin CT1250

 

 

 

 

                                                                       User Guide

 

 

Rev: 08    07-19 

7  

4

 

Panel LED Status 

 

 

Power  

When the system is connected to the mains supply, 
the Power LED will illuminate.  
If no power is present, this LED will not light up.  
 

 

Gas on  

When the fans are running at the correct speed and 
the key switch is turned on, the CT1250 will open the gas valve and the green LED will illuminate.

 

 

ON = Gas On     
OFF = Gas Off  

 

EM Stop  

If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate 
AMBER and the gas will be turned off.  
OFF = OK  
ON = Emergency Stop button pressed – De-press the button and reset the system. 

 

Supply Fan  

Under normal working the LED will illuminate GREEN. If a supply fan fault is present, the LED will be 
flashing. If the LED flashes for more than 20 seconds, the gas will be shut off. 
ON = OK  
FLASHING = the supply fan is not running. 

 

Extract Fan 

Under normal working the LED will illuminate GREEN. If a supply fan fault is present, the LED will be 
flashing. If the LED flashes for more than 20 seconds, the gas will be shut off. 
ON = OK  
FLASHING = the extract fan is not running. 

 

Fan Fault 

Under normal working conditions this LED is off. If a fan fault is present for more than 20 seconds, 
the LED will illuminate AMBER. 
OFF = OK  
ON = the gas supply has been shut off due to a ventilation fault.  
 

IF A FAULT IS FOUND YOU WILL NEED TO CONTACT YOUR SERVICE/MAINTENANCE COMPANY. 

YOU SHOULD NOT ATTEMPT TO CARRY OUT A REPAIR UNLESS YOU ARE QUALIFIED TO DO SO. 

 

 

Service LED 

When the service light is illuminated green this means the service dip switch inside the Merlin 
CT1250 has been placed in the ON position. 
This will allows the gas valve to remain open for 4 hours without the fans running on each 
activation of the key.  
ON = Service switch activated.   
OFF = Service switch de-activated. 
FLASHING = at the end of the 4 hours the gas will shut off and the service LED will flash. 
 

Содержание Merlin CT1250

Страница 1: ...Merlin CT1250 User Guide Rev 08 07 19 1 Merlin CT1250 Ventilation Interlock System with Current Monitoring User Guide Please read this guide carefully and retain for future use...

Страница 2: ...4 Remote Emergency Buttons 4 2 5 Supply and Extract Fan PD Switches 4 2 6 Fan current monitoring 5 2 7 Potentiometers 5 2 8 Service Mode Switch 5 3 Operation 6 3 1 System ON and OFF 6 3 2 Emergency Sh...

Страница 3: ...ard The PCB should be removed before drilling entry holes into the case Important Warning Statements Never ignore your device when in alarm This device requires a continual supply of electrical power...

Страница 4: ...fans audible alarms etc Detailed on the circuit board as TO BMS normally closed N C common COM and normally open N O These are volt free connections 2 4 Remote Emergency Buttons The terminal for remot...

Страница 5: ...SENS2 Potentiometer The fan s should be run at the minimum required speed and the relevant potentiometer turned slowly clockwise until the green LED on the circuit board lights up This indicates the...

Страница 6: ...ke or break a circuit on gas on gas off valve open or valve closed This will tell the BMS whether or not the kitchen has use of the gas supply 3 4 Fire Alarm Integration The Merlin CT1250 can be integ...

Страница 7: ...running Extract Fan Under normal working the LED will illuminate GREEN If a supply fan fault is present the LED will be flashing If the LED flashes for more than 20 seconds the gas will be shut off ON...

Страница 8: ...Merlin CT1250 User Guide Rev 08 07 19 8 5 Troubleshooting...

Страница 9: ...e any accumulated dust from the outer enclosure once a month NEVER use detergents or solvents to clean your device this may permenantly or temporarily damage the panel NEVER spray air fresheners hair...

Страница 10: ...Merlin CT1250 User Guide Rev 08 07 19 10...

Страница 11: ...Merlin CT1250 User Guide Rev 08 07 19 11...

Страница 12: ...liable for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the consumer or any other user of this product whether due to a...

Отзывы: