Circuit Board Terminals 

 

 

2.1

 

POWER 

A 110-240VAC electrical supply should be externally fused at 3A 
and connected to the terminals marked [POWER LNE].  
 
2.2

 

 GAS VALVE 

The 110-240VAC gas solenoid valve should be powered using 
the terminals on the Merlin 1000S detailed [GAS VALVE LNE]. 
 

 

2.3

 

BMS OUT 

Terminal connections are available on the circuit board for Building 
Management systems etc.  
 
Detailed on the circuit board as [BMS OUT - N/C, COM and N/O] 
(Normally Closed / Common / Normally Open). 

 

These are volt free connections. 

 

This is a relay that changes state in alarm or when the gas is on/off and can be used in 
conjunction with the 12vDC output and other external relays that affect other devices and 
controls such as purge fans and audible alarms etc. 
 
 
2.4

 

PRESSURE SENSOR

 

This terminal is connected to the gas pressure transducer as shown which 
is then screwed into the downstream port on the gas solenoid valve.   
         
 
 
 
 
 
 
Min Operating Pressure = 12mbar 
Max Operating Pressure = 100mbar 
 
 
 
 

ENSURE THIS IS SCREWED TO THE DOWNSTREAM PORT OF THE GAS SOLENOID VALVE. 

 
 
 
 

Содержание Merlin 1000S

Страница 1: ...Merlin 1000S User Guide Rev 07 05 19 1 Gas Safety Products Merlin 1000S Gas Proving Detection System User Guide Please read this guide carefully and retain for future use...

Страница 2: ...MOTE 5 2 6 GAS DETECTOR 5 2 7 FS 1 2 3 4 5 2 8 CO2 MONITOR 5 2 9 12v DC 5 3 Installation Operation 6 3 1 System On and Off 6 3 2 Emergency Shut Off 6 3 3 BMS Integration 6 3 4 Auto shut down Timeout f...

Страница 3: ...oved before drilling entry holes into the case Important Warning Statements Never ignore your device when in alarm This device requires a continual supply of electrical power it will not work without...

Страница 4: ...e circuit board as BMS OUT N C COM and N O Normally Closed Common Normally Open These are volt free connections This is a relay that changes state in alarm or when the gas is on off and can be used in...

Страница 5: ...3 4 This terminal switches when the key is turned on and off This can be linked to a fan switch supplied separately which can provide power to the fans when the control panel is switched on 2 8 CO2 M...

Страница 6: ...gas on gas off valve open or valve closed This will tell the BMS whether or not power is being sent to the solenoid There is a dip switch located on the inside facia of the panel labelled BMS SEL This...

Страница 7: ...ation this can be switched to ON this will instruct the system to leave the fans on and only shut off the gas supply on activation of the Emergency shut off button s Note This option is not available...

Страница 8: ...nate ON Gas On OFF Gas Off Testing This LED will illuminate GREEN for approximately 30 seconds when the panel is checking the integrity of the gas installation upon start up ON proving the gas line do...

Страница 9: ...s will show RED and the Gas valve will turn off OFF OK ON Gas detected CO2 High Under normal working conditions this LED is off If the concentration of CO2 in the air is at alarm level relevant detect...

Страница 10: ...Common and Normally Open 8 PRESSURE SENSOR Gas pressure transducer power supply and returned signal supplied 9 EM REMOTE Remote emergency stop buttons and Fire Alarm input wired in series purchased se...

Страница 11: ...Merlin 1000S User Guide Rev 07 05 19 11...

Страница 12: ...liable for loss of use of this product or for any indirect special incidental or consequential damages or costs or expenses incurred by the consumer or any other user of this product whether due to a...

Отзывы: