background image

 

 

S&S Northern Ltd. Wallace Francis House, Barnes Wallis Way, Buckshaw Village, Lancashire, PR7 7JN T. 01257 470983 www.snsnorthern.com 

 

 

STEP 8 Flow Per – Press ok to cycle through the options. This is the setting the controller uses to measure the values en-
tered in steps 2 and 3. [We generally use hour or half hour as these are the most granular setting and give the most pro-
tection. We have used half hour in this example] E.g. if you entered 100ltr the system will allow 100ltr per half hour to 
pass through before going into alarm. [This is NOT at set intervals that start on the hour or half hour (12.00, 12.30, 13.00, 
13.30 etc). It uses a clever algorithm to constantly monitor volume used in any period of 30 minutes].  
 
STEP 9 Pulse – Press ok to cycle through the options. This must match the pulse output from the connected meter(S). 
[Generally smaller meters will be 1ltr per pulse and larger flanged meters 10 ltrs per pulse. This information is normally 
found on the water meter. You cannot use meters that do not have a volt free pulse of 1, 10 or 100 ltrs on this controller. 
We have selected 1]  
 
STEP 10 Valves – Press ok to cycle through options. If a valve is fitted to the system select the channel you have connect-
ed the valve to [ignore this setting if no valve fitted. We selected none].  
 
STEP 11 Meters – Press ok to cycle through options. Select dependent on whether you have one or two meters connect-
ed. [1 meter fitted use channel 1 and select 1 only, two meters fitted select both. We selected both].  
 
For 99.9% of installations you have now finished setting up.  
 
An overview of the system as programmed above:  

 

Between 6am and 6pm every day up to 100ltr per half hour can be used until an alarm  

 

From 6pm through to 6am the next day 50ltr per half hour can be used before an alarm.  

 
Home screen:  

 

Are the date and time correct? [if not, your time periods will be out. Please be aware this unit does not self-adjust 
between GMT and BST]  

 

Guard: Low [assuming you are in the low guard time period, if not unit will display ‘Timer high’. It is possible to put 
the unit into manual high guard by pressing ok. Press ok again to go back to programmed settings]  

 

Channel 1: OK [if display is ‘closed’ select channel using down button and press ok, should display ‘changing’ then 
display ‘ok’]  

 

Channel 2: OK [as channel 1. If you selected 1 meter in step 11, no channel 2 will be displayed]  

 
Modes Screen: Press R/H arrow once to enter  

 

Mode: Normal [It is possible to select ‘Permanent High’ by pressing ok (this will change the guard display on the 
home screen to ‘Permanent High’). If selected the unit will stay in hi guard until reversed]  

 

Power: should say mains [unless you are running on battery back up, in which case it will say battery]  

 

Meter 1: Will display the amount you entered in step 5 (unless water has been used). [An easy way to check you 
have the correct pulse setting is to run off some water in the building and check this reading continues to match 
the reading on the top of the water meter].  

 

Meter 2: As meter 1 above [If you selected 1 meter in step 11 no meter 2 will be displayed]  

Содержание ATWM

Страница 1: ...ter meter If the volume of water reaches the pre set limit customer adjustable the system can isolate the mains water pipe therefore limiting the amount of water and leak damage INSTALLATION ITEMS NOT...

Страница 2: ...y Ensure compound does not enter valve Avoid pipe strain by proper support and align ment Type PN16 mating flanges will be required on some models over 50mm E HELPFUL HINTS We recommend that AT WM is...

Страница 3: ...The Output connections can be used to activate an external alarm auto dialler or connection to a BMS The AT WM controller monitors the water flowing ONE or TWO water meters or flow switches There are...

Страница 4: ...and one solenoid valve If two are required the second set should be wired to the Valve 2 terminals Diagrams shown are for one water meter solenoid valve When two are required use Valve 2 terminals for...

Страница 5: ...in litres hour default 2 LO GUARD VAL As above but for when the property is occupied default 50 OVERRIDE TIME Push OK to increase from 10 minutes to 45 minutes maximum default 30 METER READINGS Push...

Страница 6: ...read the AT WM installation instructions for information on installing connecting and navigating around the menu system All values used in this guide are examples only and NOT definitive settings your...

Страница 7: ...s is the higher value of the two for when the building is expected to use the most water Use left and right arrows to enter higher values faster We select ed 100 Press ok to exit back to menu STEP 4 O...

Страница 8: ...annel 1 and select 1 only two meters fitted select both We selected both For 99 9 of installations you have now finished setting up An overview of the system as programmed above Between 6am and 6pm ev...

Отзывы: