3.3.
Remote Switching
The switching between the (up to) three speeds can be activated by either:
(Up to) Three Volt-free contacts, or
(Up to) Three 230V supply inputs
On/Off – Volt-Free Contact and/or 230V
External Fire Fan Shut-Off Switch – An external “Fire” switch (Volt-Free) can be connected, If the
switch opens signifying that the fire alarm has been activated, then the MULTI-REG Controller will
automatically stop the fan.
3.4.
Fan-Fail Detection by Fault Sensing
Automatic monitoring of the impeller rotation via the Tacho pulse (frequency generator) signal.
Low current sensing to indicate a connection open circuit problem.
Sixty seconds time-delay of fault detection on start-up to allow input levels to normalise.
Facility to connect an Airflow Switch or Differential Pressure Switch (DPS), for use on fans where
other options are not practical. There is approximately a 60 seconds delay in the operation of the
airflow switch monitoring system, to allow full airflow to develop.
3.5.
Outputs
Digital Display
Running, Stopped and/or fault condition.
Fan speed percentage and 0-10V output condition.
Countdown to fault status monitoring condition (allows fan to gain speed).
Diagnostic – Reasons for fan stop/fail.
3.6.
Analog Switch Outputs
Output to BMS of fan run and fault indicated by an individual set of contacts capable of controlling
a maximum load of up to 230 Volts at 8 Amps.
Provision to operate a system damper actuator (can be supplied as an accessory). When the fan
is running, the damper opens, when the fan is stopped (either intentionally or in a fault condition)
the actuator spring return facility closes the damper.
4.
SAFETY RULES
4.1.
WARNING
Mains voltage is present. It is the responsibility of the user to ensure compliance with the Health
and Safety at Work Act, 1974.
Isolate mains supply before connecting.
4.2.
CAUTION
This unit must be earthed.
All electrical connections should be made by a qualified electrician.
All wiring must be in accordance with current wiring regulations. The control should be provided
with a separate double pole isolator switch.