CONTROL PANEL

0

I

On/Off Switch

Power to unit
Indicator

Fan speed
Switch

Water overflow
Indicator

Fan only Switch

Figure 10. Layout of control panel on pillar

6.

MAINTENANCE AND FAULT FINDING

Electrical and refrigerant work should only be carried out by competent engineers. Work which is not
conducted in accordance with the information contained in these instructions may result in the
warranty becoming void.

: Carry out at intervals not exceeding 4 months or more often if in a dirty

environment. The upper front panel carrying the inlet grille should be removed to gain access to the
filter. This panel is carried on a number of studs, and can be removed by hinging and lifting forward
after unlocking. The filter can be removed from the retaining bracket and cleaned. This involves
gentle tapping to remove accumulated dust and cleaning with a vacuum cleaner. The filters can
also be washed in soap and water and air-dried. Replacement filters are available (see Spares List).

: Carry out at intervals not exceeding 4 months or more often if in a dirty

environment. The side panel should be removed to gain access to the drain pan. The drain pan is
located underneath the evaporator coil, and can be removed by gently twisting the slotted plastic
bracket holding it in place. The drain pan can be cleaned with any proprietary-cleaning agent. For
replacement, reverse the above process.

The panels must never be removed when the mains power is connected. Turn the dehumidifier off
and either remove the plug from the socket or isolate the supply when access is required.

6.1 Maintenance

Cleaning of filter

Cleaning of drain pan

Page 15

QA/IOM/46 Issue 11 - MD Dehumidifier

Содержание MD

Страница 1: ...INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS MD DEHUMIDI FIERS QA IOM 46 Issue 11 MD Dehumidifier...

Страница 2: ...Refrigeration system 5 1 3 Fan and ventilation system 6 1 4 Safety features 6 1 5 Performance 7 3 1 Siting of the dehumidifier 9 3 2 Changing from pump to gravity condensate discharge 10 3 3 Fan only...

Страница 3: ...in through a filter and across the evaporator and discharge it through the condenser Moisture is removed from the entering humid air at the evaporator coil and it is collected in a drain pan mounted...

Страница 4: ...Page 4 Figure 3 Front view with front panel removed Figure 4 Side view with side panel removed QA IOM 46 Issue 11 MD Dehumidifier...

Страница 5: ...lter This panel sits on the lower front panel supported by studs and is removed by using the keys provided to unlock the panel and hinging forward The control panel allows switching between different...

Страница 6: ...t never be operated with any of the panels removed Great care should also be taken to avoid damage to the seals on the panels To protect the compressor from hunting a start delay has been built into t...

Страница 7: ...ge of operating conditions is shown in the curves below o o 100 unit 0 50 100 150 200 20 25 30 35 40 45 Temperature C litres day 40 RH 60 RH 80 RH 160 unit 0 50 100 150 200 250 300 20 25 30 35 40 45 T...

Страница 8: ...the required rate Place the condensate discharge hose in an appropriate drain If the dehumidifier is to be discharged by pump then the drain should not be more than 2 metres above the base of the dehu...

Страница 9: ...fier is to be discharged by pump then the drain should not be more than 2 meters above the base of the dehumidifier If the dehumidifier is to discharge by gravity then the hose must be laid on the flo...

Страница 10: ...ently required Fit the longer length of hose supplied with the unit to the spigot on the drainpan using the clip supplied Pass the hose through the lower of the two round holes in the base of the pill...

Страница 11: ...ressor cutting in after the delay period The speed of the fan can be changed from full to slow using the switch on the front panel see figure 10 At slow speed the dehumidification rate is lower than a...

Страница 12: ...FIGURE 7 WIRING DIAGRAM FOR THE MD100 Page 12 QA IOM 46 Issue 11 MD Dehumidifier...

Страница 13: ...FIGURE 8 WIRING DIAGRAM FOR THE MD160 Page 13 QA IOM 46 Issue 11 MD Dehumidifier...

Страница 14: ...FIGURE 9 WIRING DIAGRAM FOR THE MD200 Page 14 QA IOM 46 Issue 11 MD Dehumidifier...

Страница 15: ...from the retaining bracket and cleaned This involves gentle tapping to remove accumulated dust and cleaning with a vacuum cleaner The filters can also be washed in soap and water and air dried Replace...

Страница 16: ...ompressor start time delay to complete Wait for defrost cycle to complete Pump drain pan full Turn off at switch on control panel and mains Check condensate hose is not blocked or kinked Check pump gr...

Страница 17: ...in is too small and is causing hunting move the dehumidifier to a larger space or address the source of the moisture generation Local supplier Telephone fax support Please quote Supplier Model Type a...

Страница 18: ...S P Coil Products Ltd SPC House Evington Valley Road Leicester LE5 5LU Tel 0116 249 0044 Fax 0116 249 0033 e mail spc spcoils co uk Web www spcoils co uk QA IOM 46 Issue 11 MD Dehumidifier...