SETUP
Press and hold [MODE] for 3 seconds to enter setup mode.
OR
01 Optional Duct Heater (Default: heater disabled)
Press [
▲]/[▼] to enable or disable duct heater.
Press [SET] to confirm settings.
OR
02 Temperature Unit (Default: degrees F)
Press [
▲]/[▼] to select degrees C or degrees F.
Press [SET] to confirm settings.
OR
OR
03 Humidity/Temperature (Default: temperature and humidity)
Press [
▲]/[▼] to evaluate temperature only, humidity only or both
temperature and humidity.
Press [SET] to confirm settings.
OR
04 Optional Motorized Damper (Default: motorized damper disabled)
Press [
▲]/[▼] to enable or disable motorized damper.
Press [SET] to confirm settings.
OR
05 Optional Thermostat Integration (Default: standalone system)
Press [
▲]/[▼] to enable or disable thermostat integration.
Press [SET] to confirm settings.
06 Fan Run Time per Hour (Default: 15 minutes)
Press [
▲]/[▼] to adjust 5-60 Minutes/Hour (Increments of 5).
Press [SET] to confirm settings and return to normal mode.
All setting screens will return to the normal mode screen automatically after
20 seconds.
FUNCTION SETTINGS
Press <Set> key to set the temperature/humidity limits and duct heater set
point.
FACTORY RESET
Press and hold [
▲]&[▼] buttons in OFF mode for ~5 seconds to
reset the control to factory settings.
will be displayed on the
screen when complete.
FEATURES
◆
Voltage supply: 24VAC +/- 15% 50/60Hz
◆
System mode: Off / On / Eco
◆
Temperature unit mode:
F or
C
◆
Temperature measurement range: 15
F - 130
F (-10
C to
55
C)
◆
High Limit Temperature settings range: 65 -105°F (18
C to
40
C)
◆
Low Limit Temperature settings range: 20 - 60°F ( -6
C to
16
C)
◆
Heater Temperature settings range: 32°F - 62°F (0°C -
16°C)
◆
Temperature resolution: 1 °F or 0.5
C
◆
Temperature Accuracy: +/-1 °F or 0.5
C
◆
Humidity measurement range: 10-95%
◆
High Limit Humidity settings range: 55-90%
◆
Low Limit Humidity settings range: 10-50%
◆
Humidity resolution: 1 %
◆
Humidity Accuracy: +/- 5 %
◆
10 inch RJ11 (6 wires) phone cable for humidity sensor
◆
10 inch 26AWG (2 wires) cable for temperature sensor
◆
Max Sensor Wire Length: 300 feet (100m)
◆
Motorized Damper relay output (Maximum 2A)
◆
Fan relay output (Maximum 2A)
◆
Duct Heater relay output (Maximum 2A)
◆
Furnace Blower Output (Maximum 2A)
◆
Non-volatile memory to store settings, configuration
parameters
◆
Operating temperature: 15
F to 130
F (-10
C to 55
C)
◆
Storage temperature: -20
F to 158
F (-29
C to 70
C)
◆
Temperature limit of mounting surface: 130
F (55
C)
◆
Terminals: 2.5mm
2
cable
◆
Pollution Degree: 2
◆
Degree of protection: IP20
◆
Electronic control: Type 2.B
◆
Class II Control
◆
cULus listed: UL60730-1
◆
Housing Material: Lexan 943(f1), 1.6mm thick, V-0 (UL94
Rating)
◆
Time Setting Rage: 5-60 Minutes
◆
Power: 1.5W (Max)
200103
Press [
▲]/[▼] to change the high limit
temperature setting.
Press [SET] to confirm settings.
Press [
▲]/[▼] to change the high limit
humidity setting.
Press [SET] to confirm settings.
Press [
▲]/[▼] to change the low limit
temperature setting.
Press [SET] to confirm settings.
Press [
▲]/[▼] to change the duct heater
activation temperature setting.
Press [SET] to confirm settings and return to
normal mode.
Press [
▲]/[▼] to change the low limit
humidity setting.
Press [SET] to confirm settings.