SETUP 

Press and hold [MODE] for 3 seconds to enter setup mode.

 

  OR 

 

01 Optional Duct Heater (Default: heater disabled) 
Press [

▲]/[▼] to enable or disable duct heater. 

Press [SET] to confirm settings.

 

 

  OR 

 

02 Temperature Unit (Default: degrees F) 
Press [

▲]/[▼] to select degrees C or degrees F. 

Press [SET] to confirm settings.

 

 

  OR 

  OR 

 

03 Humidity/Temperature (Default: temperature and humidity) 
Press [

▲]/[▼] to evaluate temperature only, humidity only or both 

temperature and humidity. 
Press [SET] to confirm settings.

 

 

  OR 

 

04 Optional Motorized Damper (Default: motorized damper disabled) 
Press [

▲]/[▼] to enable or disable motorized damper. 

Press [SET] to confirm settings.

 

 

  OR 

 

05 Optional Thermostat Integration (Default: standalone system) 
Press [

▲]/[▼] to enable or disable thermostat integration. 

Press [SET] to confirm settings.

 

   

   

06 Fan Run Time per Hour (Default: 15 minutes) 
Press [

▲]/[▼] to adjust 5-60 Minutes/Hour (Increments of 5). 

Press [SET] to confirm settings and return to normal mode.

 

 

All setting screens will return to the normal mode screen automatically after 
20 seconds. 

 

FUNCTION SETTINGS 

Press <Set> key to set the temperature/humidity limits and duct heater set 
point.

 

 

 

 

 

 

 

 

 

 

 

 
 

 
 
 

FACTORY RESET 

Press and hold [

▲]&[▼] buttons in OFF mode for ~5 seconds to 

reset the control to factory settings. 

 

will be displayed on the 

screen when complete. 

FEATURES

 

 

Voltage supply: 24VAC +/- 15%   50/60Hz 

 

System mode: Off / On / Eco 

 

Temperature unit mode: 

F or 

 

Temperature measurement range: 15

F - 130

F (-10

C to 

55

C) 

 

High Limit Temperature settings range: 65 -105°F (18

C to 

40

C) 

 

Low Limit Temperature settings range: 20 - 60°F ( -6

C to 

16

C) 

 

Heater Temperature settings range: 32°F - 62°F (0°C - 
16°C) 

 

Temperature resolution: 1 °F or 0.5

C   

 

Temperature Accuracy: +/-1 °F or 0.5

 

Humidity measurement range: 10-95% 

 

High Limit Humidity settings range: 55-90% 

 

Low Limit Humidity settings range: 10-50% 

 

Humidity resolution: 1 % 

 

Humidity Accuracy: +/- 5 % 

 

10 inch RJ11 (6 wires) phone cable for humidity sensor 

 

10 inch 26AWG (2 wires) cable for temperature sensor 

 

Max Sensor Wire Length: 300 feet (100m) 

 

Motorized Damper relay output (Maximum 2A) 

 

Fan relay output (Maximum 2A) 

 

Duct Heater relay output (Maximum 2A) 

 

Furnace Blower Output (Maximum 2A) 

 

Non-volatile memory to store settings, configuration 
parameters   

 

Operating temperature: 15

F to 130

F (-10 

C to 55

C) 

 

Storage temperature: -20

F to 158

F (-29 

C to 70

C) 

 

Temperature limit of mounting surface: 130

F (55

C) 

 

Terminals: 2.5mm

2

 cable 

 

Pollution Degree: 2 

 

Degree of protection: IP20 

 

Electronic control: Type 2.B 

 

Class II Control 

 

cULus listed: UL60730-1 

 

Housing Material: Lexan 943(f1), 1.6mm thick, V-0 (UL94 
Rating) 

 

Time Setting Rage: 5-60 Minutes 

 

Power: 1.5W (Max) 

 
 

             

                                                                 

                   

   

 
                                                                                                                  200103 
 

Press  [

▲]/[▼]  to  change  the  high  limit 

temperature setting.   
Press [SET] to confirm settings.

 

Press [

▲]/[▼] to change the high limit 

humidity setting.   
Press [SET] to confirm settings.

 

Press [

▲]/[▼] to change the low limit 

temperature setting.   
Press [SET] to confirm settings.

 

Press  [

▲]/[▼]  to  change  the  duct  heater 

activation temperature setting.   
Press [SET] to confirm settings and return to 
normal mode.

 

Press  [

▲]/[▼]  to  change  the  low  limit 

humidity setting.   
Press [SET] to confirm settings.

 