17
5.
UNIT STATUS OUTPUT WIRING
The unit status output wiring has four outputs that can go back to a building management system, the relay outputs
are a run, fault, filter and sensor relay. The contacts is normally open, with the following diagrams providing the
functionality and connection details.
The fault relay will operate depending on the following faults:
Fault Number
Description
1
Electrical heater over-heating
2
Antifreeze protection of water heating
3
Supply fan error
4
Exhaust fan error
5
Regenerator freezing
6
Temperature sensor error – Supply (SUP)
7
Temperature sensor error – Space (MB)
8
Temperature sensor error – Drain (ETA)
9
Temperature sensor error – Outdoor (ODA)
10
Temperature sensor error – Comparative (COMP)
11
Temperature sensor error – Water (RTN)
12
Temperature sensor error – Waste (EHA)
13
Temperature sensor error – External (EXT)
14
Temperature sensor error – Space (CP)
15
Controller battery low
16
SD card error