45
14. MAPA MODBUS / MODBUS MAP / CARTE MODBUS
Input registers (Read)
Register
Discrete input
Data type
Range
Default
Comments
HEX
DEC
0FFFh
4095
Current room temperature
16bits
0-255
-
0
0°C
1
0,5°C
...
100
50°C
101
51,5°C
...
1000h
4096
Current outlet temperature
16bits
0-255
-
0
0°C
1
0,5°C
...
100
50°C
101
51,5°C
...
1001h
4097
Current media temperature
16bits
0-255
-
0
0°C
1
0,5°C
...
100
50°C
101
51,5°C
...
1002h
4098
Motor type
BIT
0-1
0
0
AC version
1
EC version
1003h
4099
Door contact status
BIT
0-1
-
0
Door opened
1
Door closed
1004h
4100
Fan status
16bits
0-3
-
0
Fan off
1
Speed 1
2
Speed 2
3
Speed 3
1005h
4101
BIT error array
-
-
b6: Outdoor temp. Sensor error
b5: Slave curtain error
b4: Anti-frost protection active
b3: Door curtain communication error
b2: Outlet sensor error
b1: Room sensor error
b0: Motor error
1006h
4102
Outdoor sensor temp.
16bits
-127 – 128
—
-127
-63,5°C
-126
-63°C
...
-1
-0,5°C
0
0°C
1
0,5°C
...
128
99°C
129
99,5°C
1007h
4103
Temperature setpoint
16bits
0-255
-
0
0°C
1
0,5°C
...
100
50°C
101
51,5°C
...
1008h
4104
Controller status
-
-
b7: Electric version
b6: Door contact active
b5: Outdoor temp. sensor active
b4: Weekly timer active
b3: Heating active
b1: Panel ON
1009h
4105
Control device version
16bits
0-255
123
1.23 version