Independent control of supply and extract fans
Supply fan
Extract fan
6.6.4.2. VAV Control (variable airfl ow), with CO
2
sensor or similar
FIRE DANGER
For DI heat recovery units, equipped with electric post heating battery, the installer
must ensure that the minimum airfl ow is enough to prevent electrical battery over-
heating. We recommend that minimum airfl ow was not less than 1/3 part of the heat
recovery unit nominal airfl ow.
All CADB-HE are equipped with EC motors, single-phase 230V power on models 04 to 27
and three-phase 400V on models 33 to 100. The motors have specifi c terminals for sending
a regulation signal to control fan speed (0-10V). The 0V signal corresponds to the fan stop,
while the signal of 10V corresponds to fan maximum speed.
To perform the speed regulation in VAV with speed control with external sensor of CO2 or si-
milar, it is necessary to use the accessory CONTROL AERO-REG and the external sensor (see
point 7.5.2.4.). In the CONTROL AERO-REG instruction booklet it is contained the necessary
information to carry on the electrical connection of the different components.
6.6.4.3. CAV control (Constant airfl ow)
The inverter is used to guarantee an specifi c constant air volume in the duct system, regard-
less of the fi lters clogging state.
All CADB-HE are equipped with EC motors, single-phase 230V power on models 04 to 27
and three-phase 400V on models 33 to 100. The motors have specifi c terminals for sending
a regulation signal to control fan speed (0-10V).