SANDENVENDO AMERICA INC
1213686f ECN 55522
9
Push the I/O button to turn on the HFD and lock in this setting.
Ambient Temperature Display
To turn the ambient temperature display on or off: with the controller on, press and hold the Time
button and press the I/O button. (This feature is disabled in firmware revision 4.01).
Front Door
If the front door is opened (HFD6 and 7 only), the controller turns off only the lights. The display
reads "OPEn". After closing the front door, the lights turn on, and the display reverts to internal
ambient temperature.
Heater Temperature Adjustment
Push the I/O button to turn the unit off. The lights inside the HFD will turn off.
With controller power off, hold down the Time button, then press and hold the I/O button until the
display comes on. The display will show the firmware revision.
Push either of the two buttons corresponding to the shelf that you wish to change the temperature.
Both lights on either side of the buttons will begin blinking.
Push and hold the button on the left to decrease the temperature (shown on the display).
Push and hold the button on the right to increase the temperature (shown on the display).
Repeat the procedure using the buttons that correspond to each of the six shelves (for HFD6 & 7), or
four shelves (HFDM).
Once the temperatures are adjusted for each of the separate zones, push the I/O button to lock in
the new temperature settings and to turn the HFD back on (the lights in the HFD will come on).
Error Codes
E30 Internal ambient thermistor open circuit
E60 Upper left shelf thermistor open circuit (except HFDM) E63 Upper right shelf thermistor open circuit
E61 Middle left shelf thermistor open circuit (except HFDM) E64 Middle right shelf thermistor open circuit
E62 Lower left shelf thermistor open circuit
E65 Lower right shelf thermistor open circuit
E90 Unable to read USB drive (check vendo.cfg for file format error)
E70 Upper left shelf not heating (except HFDM)
E73
Upper right shelf not heating
E71 Middle left shelf not heating (except HFDM)
E74
Middle right shelf not heating
E72 Lower left shelf not heating
E75
Lower right shelf not heating
Clear the error by powering off the unit, correcting the problem, and turning the unit on again.
Programming using USB drive
The file name must be vendo.cfg and be saved on the root directory of the USB drive. The file may
be edited using Notepad.
Temperature and Timer Programming Format and Download
SV01
Must be SV01
001h
This is configuration 001, h for standard HFD (n for HFDM, c for HFDC, etc.)
UL:235,2:00,0:30
U
pper
L
eft shelf, set to 235ºF, left timer 2 hours, right timer 30 minutes
ML:235,2:00,2:00
Shelf temperatures may be set between 100 and 255ºF
LL:220,1:00,2:00
Setting a shelf temperature to 000 turns off that shelf
UR:235,2:00,1:00
Shelf temperature must be 3 digits, always in ºF
MR:235,2:00,2:00
Each timer may be set between 0:30 and 4:00
LR:220,1:00,2:00
CF:1
1 displays ºF, 0 displays ºC
DA:1
1 turns on controller ambient display, 0 turns display off
DS:1
Front door switch
– 1 for HFD6 & 7; all others 0.