Sanden
Heat
Pump
–
Service
Technical
Book
Page
33
of
48
Check Points
Error
Code
Error Contents
Error Detection Condition &
Diagnostic
Connector
No. or
Maintenance
Monitor No.
Connector
Colour
Judgment & Repair Methods
E124
Power cutoff detected in
compressor operation control
㩷
㩷
㩷
㩷
<Check Items>
㩷
㩷
㩷
㩷
- Check for HP control PC board
connector connection
㩷
㩷
- Confirm connector connections
㩷
- Error in compressor wiring
㩷
㩷
- confirm connection of wire terminals
to compressor is in the right order
㩷
- Error in connection on power
supply terminal block
㩷
㩷
- Confirm cable is connected
correctly at terminal block
㩷
- Power cutoff occurred
㩷
㩷
- Check Power supply cable wiring
layout
㩷
- Power supply voltage error
㩷
㩷
- Confirm power supply voltage
(240+/-14V)
㩷
INV Transient Power
Cutoff Detection Error 2
- PC board malfunction
㩷
㩷
- PCB replacement required if same
error occurs again after re-run of heat
pump
E125
Error detected inside PC board
㩷
㩷
㩷
㩷
<Check Items>
㩷
㩷
㩷
㩷
INV Control Circuit Board
Power Supply Error
- PC Board malfunction
㩷
㩷
- PCB replacement required if same
error occurs again after re-run of heat
pump
E130
Wire break or short circuit
detected on thermistor in HP
control PC board
㩷
㩷
㩷
㩷
<Check Items>
CN1
White
㩷
㩷
- Thermistor wiring error
㩷
㩷
- Confirm connector connections
㩷
INV Temperature Sensor
Error
- malfunction of thermistor on HP
control PC board
㩷
㩷
- PCB replacement required if same
error occurs again after re-run of heat
pump
E131
90degC or more detected by
thermistor on HP control PC
board
㩷
㩷
㩷
㩷
<Check Items>
㩷
㩷
㩷
㩷
- No fan blade rotation
㩷
㩷
- Check fun motor rotation
㩷
㩷
㩷
㩷
- Confirm connector connections
㩷
- No efficient air absorption
amount
㩷
㩷
- Check if any damege on propellar
fan blade
㩷
㩷
㩷
㩷
- Remove foreign object from
evaporator if any
㩷
INV Heatsink
Temperature Error
- Fan motor malfunction
㩷
㩷
- Replace fan motor