14 S&C Instruction Sheet 461-508LD
Controller Module Specifications
The TripSaver II Cutout-Mounted Recloser contains
a controller module used to control the self-powered
recloser. The controller module processes all electronic/
electrical functions required for the proper operation of
the TripSaver II recloser. The controller can be wirelessly
accessed and configured via the IEEE 802.15.4 protocol.
See Figure 17 and Table 2.
E
D
C
B
A
Figure 17. Controller module pinout diagram for Table 1.
Label
Description
Voltage
A
J10, Input Connection
●
11-14 .5 Vdc 1 A
B
J12, Rogowski Coil Connection
12 Vac
, < 10 mA
C
J9, Dropout Control Connection 225 Vdc , 5 A
D
J8, VI Control Connection
225 Vdc , 5 A
E
J2, CT Input Connection
230 Vac
, 2 A, 50/60
Hz
●
J10 connection meets SEL V voltage levels .
---
,
---
---
Table 2. Connection Locations and Descriptions
Insulation rating for the external circuit connected
to J10:
Make sure any external circuits providing a source
of power that are connected to the unit are double- or rein-
forced-insulated from the mains or are separated from the
mains by basic insulation plus a grounded shield. They also
should meet requirements for SELV voltage levels (under
33 V RMS/46.7 V peak or 70 Vdc in normal conditions, and
55 V RMS/78 V peak or 140 Vdc single-fault).
Operating Temperature Range:
–40°C (-40°F) to
+50°C (122°F)