S&C Instruction Sheet 663-500    11

Cable Terminations

STEP  3.  

To facilitate makeup and connection of cable 
terminations to switch terminals, switch 
interphase and end barriers (where applicable) 
can be removed by loosening the wing-head 
screw that secures each barrier to the barrier-
support angle. Remove the tie wraps securing 
the wing-head screws for shipment. The screw 
will remain attached to the barrier, which is 
supported at the switch frame by the barrier 
guide. See Figure 5. Lift the barrier from the 
guide and place it in a location where the barrier 
will not be damaged.

STEP  4.  

Optional cable guides (catalog number suffi x 
“-M2” or “-M3”), if specifi ed, include cable-
support brackets (packed separately) and 
mounting angles (factory installed when an 
optional base spacer, 12-inch (30.5-cm) 
minimum, is specifi ed; packed separately 
otherwise). Using the hardware furnished, 
attach the mounting angles (if packed 
separately) to the tabs provided on the sidewalls 
of the compartments and attach the cable-
support brackets to the angles. See Figure 5. Do 
not remove the protective sheet from the saddle 
of the bracket or install the cable wrap until 
instructed to do so in Step 5 on page 13.

Figure 5. Side view of the switch showing the interphase barrier attachment points, terminal-pad connections, and installation of 
the current sensors (furnished with the optional Overcurrent Lockout feature) and optional cable guides.

Installation

Barrier-support angle

Wing-head screw

Switch interphase barrier

Connect terminator (or

connector)

 to two uppermost

holes on switch terminal pad
when catalog number suffix 
“-M2” or “-Y2” is specified

Offset spade-type

compression terminal

Cable terminator

Install current sensor using
plastic tie wraps

12-inch (305-mm)

min. base spacer or

cable pit

 (required if

catalog number
suffix “-M2” or “-M3”
is specified

Barrier guide

(not visible)

Current sensor

(furnished with
catalog number
suffix “-Y2”

Mounting angle and

cable-support bracket

(furnished with catalog
number suffix “-M2,”
catalog number suffix
“-M3” similar)

Concentric-neutral

ground wires

To ground bus

Содержание PMH

Страница 1: ...nstruction Sheet 2 Retain this Instruction Sheet 2 Proper Application 2 Warranty 2 Safety Information Understanding Safety Alert Messages 3 Following Safety Instructions 3 Replacement Instructions and...

Страница 2: ...C Source Transfer PMH Pad Mounted Gear Designate a location where you can easily retrieve and refer to this publication Proper Application WARNING The equipment in this publication is only intended f...

Страница 3: ...autions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If y...

Страница 4: ...COMPANY S C 6601 NORTH RIDGE BOULEVARD CHICAGO ILLINOIS AND NEITHER RECEIPT NOR POSSESSION THEREOF INFERS OR TRANSFERS ANY RIGHT IN OR LICENSE TO USE THIS DOCUMENT THE SUBJECT MATTER THEREOF OR ANY D...

Страница 5: ...l circuits and component parts live until completely de energized tested grounded and tagged or properly identified Do not work on or near this equipment unless you 1 Know and obey your employer s wor...

Страница 6: ...ng any device that is to be inspected replaced serviced or repaired in the high voltage compartments 9 MAINTAINING PROPER CLEARANCE Always maintain proper clearance from energized components 10 SWITCH...

Страница 7: ...ons about field programming and opera tion of the Micro AT control refer to S C Instruction Sheet 515 500 These instruction sheets along with a catalog dimensional drawing showing cable locating and a...

Страница 8: ...ed by the packing materials and will also prevent wind induced abrasion from loose cardboard Storage S C Source Transfer PMH Pad Mounted Gear should installed and energized immediately When the gear i...

Страница 9: ...socket wrench or tool when catalog number suffix B1 or B2 is specified to unlatch the Penta Latch Mechanism by rotating the actuator counterclockwise approximately 60 degrees against spring resistanc...

Страница 10: ...latched a padlock may be inserted into the hasp Placement STEP 2 At the installation site remove all separately packaged components shipped in the pad mounted gear enclosure and set them aside in a p...

Страница 11: ...the saddle of the bracket or install the cable wrap until instructed to do so in Step 5 on page 13 Figure 5 Side view of the switch showing the interphase barrier attachment points terminal pad conne...

Страница 12: ...or 14 4 kV 2 57 for 25 kV Minimum clearance from energized parts to barriers 13 for 14 4 kV 1 32 for 25 kV Minimum clearance from energized parts to electrical ground 6 152 for 14 4 kV 7 191 for 25 kV...

Страница 13: ...taping it with a suitable material Two position cable terminator adapters are provided at the fuse hinge assemblies See Figure 7 These adapters can be placed in their alternate positions when require...

Страница 14: ...elleville washers are flat Then back off one half turn Do not use lockwashers with Belleville washers For tinned copper or tinned bronze connectors Use inch galvanized steel hardware with one Bellevil...

Страница 15: ...n accordance with the wiring diagram provided The automatic source transfer scheme will not operate properly when only six current sensors are installed S C Current Sensors STEP 7 Six S C Current Sens...

Страница 16: ...alog number suffix C9 or C10 optional Remote Indication feature catalog number suffix Y4 or optional Supervisory Control feature catalog number suffix Y6 are also located in the terminal block compart...

Страница 17: ...ier support angle at the front of the switch compartment Make sure the clearance from the barriers to energized parts and from the barriers to terminator skirts conforms to the minimum dimensions spec...

Страница 18: ...barriers Prolonged exposure to corona discharge can damage the barriers and result in a flashover injury and equipment damage f Store spare SMU 20 Fuse Units or SM 4 Refill Units as applicable in the...

Страница 19: ...Testing When high voltage dielectric tests will be performed on S C Source Transfer PMH Pad Mounted Gear special precautions should be taken to prevent damage to the voltage sensors and voltage limit...

Отзывы: