S&C PMH Скачать руководство пользователя страница 12

12    S&C Instruction Sheet 662-505

Installation

STEP  6.  

Make up cable terminations following the cable-
terminator manufacturer’s instructions.

 WARNING

While the interior of Manual PMH Pad-Mounted Gear 
is protected from direct exposure to the elements, it 
is inherently an outdoor environment—and requires 
selection and application of cable-terminating 
devices accordingly . Terminations must incorporate 
adequate leakage distance between the exposed 
conductor and the stress-relief cone, across a surface 
of non-tracking material (or surface rendered non-
tracking by properly taping with a suitable material) . 
Furthermore, to maintain the rated BIL, the following 
minimum clearances are required . See Figure 6 on 
page 11:
•  From energized parts to electrical ground: 6 inches 

(152 mm) at 14 .4 kV; 7

½

 inches (191 mm) at 25 kV .

•  From energized parts to fiberglass-reinforced 

polyester barriers: 1 inch (25 mm) at 14 .4 kV; 
2

¼ 

inches (57 mm) at 25 kV

•  From terminator skirts to fiberglass-reinforced 

polyester barriers: 

½

 inch (13 mm) at 14 .4 kV; 

1

¼

 inch (32 mm) at 25 kV .

Two-position cable-terminator adapters are provided 

at the fuse hinge assemblies. See Figure 7. These adapters 
can be placed in their alternate positions when required 
for increased clearance from energized parts to grounded 
parts of the cable terminators.

Switch terminal pads are furnished with three mounting 

holes. In general, cable terminators may be connected to 
the two lower holes in the switch terminal pads. However, 
if the pad-mounted gear includes optional cable guides 
for switch terminals (catalog number suffix “-M2”), cable 
terminators must be connected to the two uppermost holes 
in the switch terminal pads. See Figure 5 on page 9.

 CAUTION

When connecting cable terminators, avoid placing 
any intentional strain on a switch or fuse terminal . It 
is important each cable-terminator connector be flat 
against the corresponding switch or fuse terminal 
pad with the bolt holes in alignment . Do not use the 
connecting bolts to pull the cables into alignment .

Figure 7. Fuse assembly showing alternate arrangement of two-
position cable-terminator adapters.

Normal position for

maximum cable-

terminating height

Alternate position for

use when required for

electrical clearance

Содержание PMH

Страница 1: ...d this Instruction Sheet 2 Retain this Instruction Sheet 2 Proper Application 2 Warranty 2 Safety Information Understanding Safety Alert Messages 3 Following Safety Instructions 3 Replacement Instruct...

Страница 2: ...l PMH Pad Mounted Gear Designate a location where you can easily retrieve and refer to this publication Proper Application WARNING The equipment in this publication is only intended for a specific app...

Страница 3: ...cautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If...

Страница 4: ...g ground for testing before energizing the switchgear and at all times when energized The ground wire s must be bonded to the system neutral if present If the system neutral is not present proper prec...

Страница 5: ...or damage 1 Notify the delivering carrier immediately 2 Ask for a carrier inspection 3 Note condition of shipment on all copies of the delivery receipt 4 File a claim with the carrier If concealed da...

Страница 6: ...Type SML 20 and SML 4Z Power Fuses Fault Fiter Electronic Power Fuses or a variety of single barrel current limiting fuses For operating instructions regarding Manual PMH Mounted Gear refer to S C In...

Страница 7: ...socket wrench or tool when catalog number suffix Bl or B2 is specified to unlatch the Penta Latch Mechanism by rotating the actuator counterclockwise approximately 60 against spring resistance until a...

Страница 8: ...the door b Pull outward on the cover of the Penta Latch Mechanism to verify the door has latched securely If it has not use a pentahead or hexhead when applicable socket wrench or tool to rotate the...

Страница 9: ...witch barriers e Level the pad mounted gear enclosure using metal shims as required between the mounting pad and the enclosure f Shim the enclosure of four compartment units until the tops of the comp...

Страница 10: ...ge 9 b Lift the barrier from the guide and place it in a location where the barrier will not be damaged STEP 5 Optional cable guides catalog number suffix M2 or M3 if specified include cable support b...

Страница 11: ...4 kV 2 inches 57 mm for 25 kV Minimum clearance from energized parts to barriers 1 inch 25 mm for 14 4 kV 2 inches 57 mm for 25 kV Minimum clearance from terminator skirts to barriers inch 13 mm for...

Страница 12: ...14 4 kV 1 inch 32 mm at 25 kV Two position cable terminator adapters are provided at the fuse hinge assemblies See Figure 7 These adapters can be placed in their alternate positions when required for...

Страница 13: ...le washer is flat Then back off one half turn Do not use lockwashers with Belleville washers STEP 7 Connect the cable concentric neutral ground wires and the ground pads inside the pad mounted gear en...

Страница 14: ...e blind tapped holes b Check the interior of the pad mounted gear Remove all foreign materials and tools that may have been mislaid and sweep the interior clear of debris c Remove the tie wraps that s...

Страница 15: ...nt by S C should be conducted at no more than 0 75 times the values shown When making ac tests the time duration for application of the test voltage should be limited to less than 10 seconds The colum...

Отзывы: