S&C Instruction Sheet 515-600 19
Features
A few field changeable items in the
Configure
menu require a non-numeric
response. In such instances, the display will be similar to this:
CONFIG: SELECT TRANSITION
OPE N
CHANGE
Here the display is indicating the
Open
option has been selected as the type of transi-
tion by which an automatic return-of-source transfer will be effected. The
Change
mes-
sage in the lower right-hand corner of the display indicates this selection can be changed.
If a change is desired, the access code will need to be entered in the same manner
described above.
After the access code has been entered, pressing the “
” or “
” key will display
the other possible selec tion(s): in this case, “CLOSED.” The ENTER key must be pressed
to accept the selection of “CLOSED” transition.
The display will now look like this:
CONFIG: SELECT TRANSITION
CLOSED
CHANGE
Some items are available only for display of information. One such item, in the
Voltage
menu, is left-source phase 2 voltage. The display will be similar to this:
VOLTS: LEFT PHASE 2
118 VOLTS
MENU/ITEM
Here the display is indicating that the actual voltage on left-source phase 2 is
118 Volts. The
Menu/Item
message in the lower right-hand corner of the display
indicates that a menu key, the NEXT item key, or LAST item key can be pressed to exit
this particular menu item.
Non-Numeric
Items
Read-Only Items