8

    S&C Instruction Sheet 1025-510

Installation

Figure 2. A GridMaster controller dimensional drawing.

Mounting the Panel-Mounted GridMaster 

Controller Inside the Enclosure

Panel-mounted GridMaster controllers can be installed in 
a wide-variety of enclosures. When the associated IED is 
provided by S&C Electric Company, the controller may be 
factory-installed inside the gear’s low-voltage enclosure. 

The panel-mounted GridMaster controller is 14 inches 

(356 mm) high, 9.25 inches (235 mm) wide, and 3.82 inches 
(97 mm) deep, flange mounted with 

3/8

-inch (9.5-mm) 

diameter mounting holes. The microgrid controller should 
be mounted in “open-construction” style so it may be easily 
connected to and serviced without requiring removal of 
the controller or surrounding equipment. The GridMaster 
controller should be mounted in an appropriate NEMA 
enclosure (or equivalent) for protection from weather, dust, 
and unintentional intrusion. When mounting the control-
ler on a swing-out panel, make sure any communications 
cables are trained and/or harnessed in such a way move-
ment of the panel will not loosen the connections. 

To mount the GridMaster controller to the enclosure:

STEP  1.  

Tap four holes at the positions shown in Figure 
2 on an interior panel of the NEMA enclosure. 
The mounting holes have a

  3/8

-inch (9.5-mm) 

diameter. 

STEP  2.  

Use a mounting screw appropriately sized for a 

3/8

-inch (9.5-mm) hole and a flat washer to secure 

the controller inside the enclosure. When 
considering placement, make sure there is 
enough room to allow for the cables to protrude 
from the face of the controller.

356 mm

330 mm

235 mm
210 mm

97 mm

83 mm

Содержание GridMaster

Страница 1: ...tion 2 Operating Considerations 2 Special Warranty Provisions 3 Warranty Qualifications 3 Safety Information Understanding Safety Alert Messages 4 Following Safety Instructions 4 Replacement Instructi...

Страница 2: ...n Sheet This instruction sheet is a permanent part of your GridMaster Microgrid Control System Designate a location where you can easily retrieve and refer to this publication Proper Application WARNI...

Страница 3: ...anty does not apply to any equipment that has been disassembled repaired or altered by anyone other than the seller This limited warranty is granted only to the immediate purchaser or if the equipment...

Страница 4: ...tant procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any portion of this instruction sh...

Страница 5: ...rsons See the Qualified Persons section on page 2 2 SAFETY PROCEDURES Always follow safe operating procedures and rules 3 PERSONAL PROTECTIVE EQUIPMENT Always use suitable protective equipment such as...

Страница 6: ...ier immediately 2 Ask for a carrier inspection 3 Note the condition of shipment on all copies of the delivery receipt 4 File a claim with the carrier If concealed damage is discovered 1 Notify the del...

Страница 7: ...with the same safety precautions that would be applied when accessing other high voltage lines and equipment Follow all locally approved safety procedures when working on or around the controller Bef...

Страница 8: ...quiring removal of the controller or surrounding equipment The GridMaster controller should be mounted in an appropriate NEMA enclosure or equivalent for protection from weather dust and unintentional...

Страница 9: ...nector on the controller STEP 2 Connect a solid copper Ethernet cable to the Ethernet 0 port on the controller The other end of the cable may be connected to either a radio a network switch or directl...

Страница 10: ...th of wire is 1000 meters 3281 feet There is no required order for use of the screw terminals When using stranded wire S C recommends coating the stranded ends with tin solder before insertion into th...

Страница 11: ...n for the opposite state Digital outputs sink capacity 10 mA On board 5 Vdc current 50 mA The screw terminals can accept 14 to 24 AWG wire When using stranded wire S C recommends coating the stranded...

Страница 12: ...s with tin solder before insertion into the screw terminals Pinouts are shown in the Module Pinouts section starting on page 15 Analog IO Port Module This module provides input and output ports to mea...

Страница 13: ...stalled on the door of the enclosure This switch will be pre installed on the enclosure door When the door is opened the contact inside the reed switch is made and the microgrid controller will detect...

Страница 14: ...are trained and or harnessed so movement of the panel will not loosen the connection STEP 3 Turn on the control power to the GridMaster controller by toggling the ON switch in the upper right hand co...

Страница 15: ...X 4 Ground 5 Ground 6 Data RX 7 Power 8 Power RS 485 Connector Module General Specifications Control Voltage 9 to 39 Vdc Operating Temperature 25 C to 70 C 13 F to 158 F Operating Humidity 95 non cond...

Страница 16: ...16 S C Instruction Sheet 1025 510 Appendix CAN Port Module Analog IO Port Module Digital Input Output Module Vdc Vdc Vdc Vdc...

Отзывы: