6
S&C Instruction Sheet 1045-568
Step 8
Return to the
Operation
screen and click
CHANGE
to
Enable
Automatic
Operation
. On the
Setup > General > Automatic Operations
screen set
Features Enabled
to
Sectiona Phase Loss
for both switches, or determine the most appropriate
setting for your application, and enable the same feature set for both switches . Enter
settings for all the other parameters . Refer to S&C Instruction Sheet 1045-530
Setup
, or
press F1 for detailed information on each parameter . Go to the
Validate/Apply
screen
and click
Apply
.
Step 9
Go to the
Setup > Communications > DNP
screen . If SCADA communication is used,
enter the required parameters . Also enter a non-zero RTU address for the 6802 that
matches the RTU address you enter in the next step . See Instruction Sheet 1045-530 for
more information about communication settings .
Step 10
Go to the
Setup > Restoration > IntelliTEAM SG > Team 1 Setup
screen . See
Figure 2 . Enter a
Team ID
and set
Team Logic
to
IT-II
. Adjust the
Return to Normal Timer
if you want to use that function .
Overhead Source-Transfer Software
Step 11
Configure
Rec 1
for
Sw 1
and
Rec 2
for
Sw 2
. Switch 1 is connected to the rear
FIC next to the bracket mount, Switch 2 is connected to the front FIC near the
enclosure door . Enter the same
RTU Address
for both
Rec 1
and
Rec 2
; use the same
RTU Address
you entered in Step 10 . Specify which switch is
Normally Closed
and
which is
Normally Open
. For the
Normally Closed
switch set the
Normal Switch
Function
to
Src/Sub
and the
Return to Normal Mode
to
Close
. For the
Normally Open
switch set the
Normal Switch Function
to
Tie/Sub
and set the
Return to Normal Mode
to
Close
. “
Close
” defines
Return to Normal
as a closed transition mode or make-before-
break . At
Return to Normal
the normally closed switch will close and then the normally
open switch will open—the feeders are temporarily tied together, but there is no outage .
Figure 2. IntelliTeam SG Setup for Team 1.