S&C Instruction Sheet 766-527LD 5
Safety Precautions
DANGER
IntelliRupter PulseCloser Fault Interrupters operate at high voltage. Failure to
observe the precautions below will result in serious personal injury or death.
The S&C 6800 Series Automatic Switch Control and IntelliCap 2000
Automatic Capacitor Control line voltage input range is 93 to 276 Vac. Failure to
observe the precautions below will result in serious personal injury or death.
Some of these precautions may differ from your company’s operating procedures
and rules . Where a discrepancy exists, follow your company’s operating procedures
and rules .
1 .
QUALIFIED PERSONS.
Access to any of the
aforementioned products must be restricted only to
qualified persons . See the “Qualified Persons”
section on page 2 .
2 .
SAFETY PROCEDURES.
Always follow safe
operating procedures and rules .
3 .
PERSONAL PROTECTIVE EQUIPMENT.
Always
use suitable protective equipment, such as rubber
gloves, rubber mats, hard hats, safety glasses, and
flash clothing, in accordance with safe operating
procedures and rules .
4 .
SAFETY LABELS.
Do not remove or obscure any
of the “DANGER,” “WARNING,” “CAUTION,” or
“NOTICE” labels .
5 .
OPERATING MECHANISM AND BASE.
IntelliRupter fault interrupters contain fast-moving
parts that can severely injure fingers . Do not remove
or disassemble operating mechanisms or remove
access panels on the IntelliRupter fault interrupter
base unless directed by S&C Electric Company .
6 .
ENERGIZED COMPONENTS.
Always consider all
parts live until de-energized, tested, and grounded .
The integrated power module (IPM) contains
components that can retain a voltage charge for
many days after the IntelliRupter fault interrupter has
been de-energized and can derive a static charge
when in close proximity to a high-voltage source .
Voltage levels can be as high as the peak line-to-
ground voltage last applied to the unit . Units
energized or installed near energized lines should be
considered live until tested and grounded .
7 .
GROUNDING.
The IntelliRupter fault interrupter
base must be connected to a suitable earth ground
at the base of the utility pole, or to a suitable building
ground for testing, before energizing an IntelliRupter
fault interrupter, and at all times when energized .
The ground wire(s) must be bonded to the system
neutral, if present . If the system neutral is not present,
proper precautions must be taken to ensure the local
earth ground, or building ground, cannot be severed
or removed .
8 .
VACUUM INTERRUPTER POSITION.
Always
confirm the
Open/Close
position of each interrupter
by visually observing its indicator .
Interrupters, terminal pads, and disconnect blades
on disconnect style models may be energized with
the interrupters in any position .
Interrupters, terminal pads, and disconnect blades
on disconnect style models may be energized from
either side of the IntelliRupter fault interrupter .
9 .
MAINTAINING PROPER CLEARANCE.
Always
maintain proper clearance from energized
components .