SETUP set.
MENU KEY
MAIN
SETUP
SET KEY
SET KEY
Illuminate No.
Password with UP, DOWN, SHIFT KEY
SET KEY
INPUT
SET KEY
TYPE : Set sensor type for temperature (PT-1, PT-2 or DCV)
Resolution of PT-1 is higher than PT-2's
RNG.HIGH/LOW : Rang of using temperature
▶ PT-1 : -50.00∼150.00℃
▶ PT-2 : -100.0∼200℃
▶ DCV : 1∼5V
It is shown, sensor type is DCV for temperature
SCL.HIGH(LOW) : Set the input range scale when input type is
DCV
SCALE : -100.0 ∼ 200.0℃
TYPE : Set sensor type for humidity (PT or DCV)
RNG.HIGH(LOW) : Rang of using Humidity
▶ PT : -10.0∼110.0%
▶ DCV : 1∼5V
It is shown, sensor type is DCV for humidity
SCL.HIGH(LOW) : Set the input range scale when input type is
DCV
SCALE : 0.0 ∼ 100.0%
4.4 SETUP
4.4.1 INPUT