Samwon Tech SU-105DA-N Скачать руководство пользователя страница 4

SAMWON ENG                                SU-103SR    /    SU-105DA Controller User Manual                                                                    Page 

4/4 

In the case of preventing to raising the temperature of refrigerator too much during 

    defrost function operation, set the factory default DOF item at the defrost stop 

    temperature value of appropriately.    If the temperature of refrigerator is getting

 

higher than DOF temperature, stop immediately 

defrost 

and start the   

normal refrigeration.     

※If the current refrigerator temperature is higher than DOF setting   

temperature, defrost function does not work. 

 

  (3)Manual Defrost 

If the compelling defrost is necessary in the normal defrost

 operation situation, 

the compelling defrost output is made during the setting time.     

②Set manual defrost time appropriately at the t item of installer

s   

setting items.     

③If you press defrost key in the front of regulator in the situation of 

defrost output OFF, defrost output will be ON during manual defrost time.   

④If you press defrost key in front of regulator during defrost operation, 

defrost will be immediately stopped and will normally operate in the 

situation of defrost output OFF. 

 
 
 

Power Voltage 

AC100~220V (50/60Hz)  ±10% 

Power Consumption

    Approx. below 5VA 

Input Sensor 

  Thermist (Allowable Line Resistance: within 5

Ω

)   

Display Method 

Temperature :  ±2% +1digit of displayed value 

Variation(dIF)    0.1℃  ~ 25.0℃ 

Control Output 

  Relay Contact Output: 

OUT1 AC250V 10A(resistance load)/contact point life time: above 
300K times (rated load) 

  OUT2 AC250V 5A(resistance load)/contact point life time : above 

300K times (rated load) 

Control Method    ON/OFF control selection 

Setting Method    Digital Method by increase & decrease key 

Other Functions 

  Sensor  input  compensation,  Delay  Timer  forward/converse 

selection, Defrost Timer 

Ambient Temp    0℃  ~ 50℃ 

Ambient humidity    Below 85% RH 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

12. Product specification

 

 

(주)삼원 ENG 의  다양한  전제품은  불량율  0.1%에  도전하고  있습니다.

 

 

 

TEL:055-321-3030 (代)  FAX:055-321-3060 

Homepage: 

http://www.31eng.kr

    E-Mail : 

[email protected]

 

 

 
 

Содержание SU-105DA-N

Страница 1: ...uld use the shield inside cable in order to prevent input noise Sensor Input compensation the current Temp is different If sensor cable is too long or sensor is old there will be temp variation At that time use current temp compensation function rSt At the current temp displayed press set for 3 seconds If dIF displayed release set In order to move to rSt temp compensation press set several times I...

Страница 2: ...imer Output Only for SU 105DA Installer setting Item OUT2 Output of SV2 OFF Output ON Range 0 1 25 0 Auxiliary delay Timer 0 300sec Auxiliary Forward converse C Cooler H Heater ManualDefrost Time 1 999Min referto11refrigerator setting ON time Defrost operating time 0 999Min Attention 0 indefinite OFF status OFF time Defrost Stop time 0 999Min Attention 0 indefinite ON status 9 Alarm Output Setting...

Страница 3: ...s displayed release set key If you press set button several times you can move to on Change the setting as below by pressing up dn and set Installer setting item Setting value description on 0 999min Select output ON time value Set as 0 continuously OFF without ON time oFF 0 999min Select Output OFF time value Set as 0 Continuously ON without OFF time If you press Set button for 3 seconds the data...

Страница 4: ...ut OFF defrost output will be ON during manual defrost time If you press defrost key in front of regulator during defrost operation defrost will be immediately stopped and will normally operate in the situation of defrost output OFF Power Voltage AC100 220V 50 60Hz 10 Power Consumption Approx below 5VA Input Sensor Thermist Allowable Line Resistance within 5Ω Display Method Temperature 2 1digit of...

Отзывы: