PAGE 14 of 61   HO-7-1237 & HO-4-1234 OIL-FIRED HEATERS 

© SAMUEL JACKSON, INCORPORATED 2003 ALL RIGHTS RESERVED

 

 

ALARM 421

 

 

MOMENTARY LOW AIR FLOW:

 This ALARM is an indication that a choke of the 

airflow is occurring.  It is displayed when the air flow switch goes off and comes back on 
in less than 3 seconds. 
 

ERROR 422

 

 

LOW AIR FLOW MORE THAN 3 SECONDS:

 This ERROR occurs when the airflow is 

interrupted for more than 3 seconds.  Verify proper airflow and adjust switch if 
necessary. 

 

ERROR 425

  

 

OIL LOW PRESSURE:

  The oil pressure fell below 45 psi. Check fuel pump rotation 

when restart is attempted. If fuel pump rotates correctly, check the following: Check for 
empty oil supply tank. Look for a closed valve in the supply pipe. Clean both of the oil 
filter screens (in the lower cabinet and on the burner). Check for oil leaks which could let 
air leak into supply pipe and cause pressure to fluctuate. Run the test program to adjust 
the oil pressure. Remember that the oil pressure determines the maximum heat output and 
that the oil pressure should be adjusted equal to the air pressure. Oil pressure higher than 
air pressure can result in smoky operation and difficulty in starting.  

 
ERROR 426  
 

OIL HIGH PRESSURE:

  A shutdown due to this error is to preve nt rupturing the fuel line 

hoses from high oil pressure (over 90 psi). Check to see if the Fuel Pressure Relief Valve 
(FPR) is jammed shut or its discharge connection is closed off. If this is not the case, 
check to see if the Oil High Pressure Switch (OHP) has been adjusted to a pressure lower 
than the setting of the FPR. 

 

 

ERROR 430  * 
 

OIL LOW PRESSURE SWITCH FAILED:

 The Oil Low Pressure Switch (OLP) failed to 

turn off when the fuel pump was off. Check the OLP to see that its contacts have not been 
bridged and that it is adjusted properly. Run the test program to check its adjustment.  

 
ERROR 431

  

 

LOW ATOMIZING AIR PRESSURE:

 The atomizing air pressure fell below 45 psi. This 

may be caused by an inadequate air compressor, a closed valve in the supply line or an 
unusual usage of compressed air elsewhere in the plant. Dependable air pressure is 
essential for the proper operation of the burner. The pressure shown on the air pressure 
gage in the cabinet should be equal to the oil pressure, normally about 60 psi. 

Содержание HO-7-1237

Страница 1: ...PAGE 2 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED SERVICE MANUAL SAMUEL JACKSON DRYAIRE HEATER HO 7 1237 OIL FIRED HEATERS HO 4 1234...

Страница 2: ...PAGE 1 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 3: ...el Train Components 39 Component List 40 20000 Remote Control Components 44 20000 Remote Control Wiring Schematic 45 20000 Remote Control Dimensions 46 20050 Diagnostic Module Dimensions 47 Adjustment...

Страница 4: ...misplaced or being used for other jobs Heater installation will then go smoothly with no delays waiting or looking for missing parts This manual gives general information on the location of thermocou...

Страница 5: ...performs six air flow tests and interlocks including tests for a jammed or jumpered air flow switch presence of electrical fan interlocks and warnings of impending chokages in the air stream To preve...

Страница 6: ...entical The heater s various operations will be displayed as the self checks and ignition sequence are performed The digital temperature controllers will energize during this sequence and complete the...

Страница 7: ...ge to the surge protector and controls in the off season it is a good idea to turn power off to the control cabinet until it is needed again ALARMS and ERRORS are fully described later in this manual...

Страница 8: ...to Figure 2 placement of the primary thermocouple on the inner radius side after an elbow will protect it from abrasion Angling the thermocouple 45 degrees in the direction of cotton flow will prevent...

Страница 9: ...is normally the high temperature limit for cotton fiber There are two temperatures displayed on each controller during burner operation The bottom number is the desired temperature It is called the se...

Страница 10: ...ature on the PRIMARY TEMP CONTROLLER is automatically adjusted based on incoming moisture content of the cotton We call this arrangement Feed Forward Control To bypass the automatic moisture controls...

Страница 11: ...l upward or downward Raising the SP up on the moisture control will provide lower drying temperatures while lowering the SP will provide higher temperatures A decal is provided on the face of the mois...

Страница 12: ...t button and switch have identical functions on both the DIAGNOSTIC MODULE and the LOCAL PANEL located in the heater cabinet This arrangement allows access to the test program from the remote control...

Страница 13: ...r logs or decrement to the latest Log entries are in a first in first out stack therefore Error Log 500 is replaced when another log event occurs Figure 6 shows a typical Error Log display Error Log 0...

Страница 14: ...ILED 433 E MODULATING MOTOR FAILS TO CLOSE 434 E MODULATING MOTOR FAILS TO OPEN 435 E LOW COMBUSTION AIR PRESSURE 436 E COMBUSTION AIR PRESSURE SWITCH FAILED 441 E FAN INTERLOCK HAS BEEN BYPASSED 442...

Страница 15: ...NG ERROR 463 E AIR HIGH TEMPERATURE LIMIT EXCEEDED 464 E HIGH TEMPERATURE AT BURNER HEAD 470 ALERT LOW PLC BATTERY 472 A FLAME SIGNAL LASTS TOO LONG AFTER SHUTDOWN 480 A HOT BOX TRASH GATE OPEN MORE T...

Страница 16: ...r ERROR until the RESET button is pressed Only one ALARM or ERROR condition is displayed at a time The oldest unacknowledged ALARM condition is shown even if the burner shuts down due to an ERROR Pres...

Страница 17: ...ressure should be adjusted equal to the air pressure Oil pressure higher than air pressure can result in smoky operation and difficulty in starting ERROR 426 OIL HIGH PRESSURE A shutdown due to this e...

Страница 18: ...LOW COMBUSTION AIR PRESSURE This error occurs when the Combustion Air Pressure Switch CAP senses insufficient combustion air pressure less than 1 inch w c during certain steps of the operating progra...

Страница 19: ...nt shutdown of the burner when the fan is stopped The installing electrician is responsible for wiring the coil of this relay to the fan circuit Sometimes the installing electrician substitutes an ele...

Страница 20: ...light on the Flame Relay ERROR 453 FLAME SIGNAL BEFORE SPARK BEFORE FUEL This ERROR is normally caused by a malfunction or tampering with the flame relay FLR ERROR 455 FLAME SIGNAL DURING SPARK BEFOR...

Страница 21: ...m may be run to determine the severity of the leak Refer to DUAL FUEL TEST SEQUENCE EXPLANATION for details Contact the factory if the leak is severe ERROR 460 DUAL FUEL MODEL GAS LOW PRESSURE SWITCH...

Страница 22: ...above the burner head This temperature sensor will only be exposed to flame or excessive heat when air through the heater is suddenly interrupted causing the flame to go in a direction other than the...

Страница 23: ...oad relay MOL1 at 6 5 amperes Verify voltage at one of the following 380 50 415 50 or 480 60 Check for low voltage condition Verify free rotation of motor shaft and fan impeller ERROR 485 FUEL PUMP MO...

Страница 24: ...only on heater cabinet end of cable E042 NO CPU BATTERY CPU battery is either missing or dead This condition does not affect burner operation but will result in a reset of time date and custom settin...

Страница 25: ...program at any time press RESET and turn the switch left momentarily then release both Killing the supply power will also exit the test program STEP 0 The PLC s battery status will be displayed durin...

Страница 26: ...want the heater to automatically shutdown Once the shutdown time has been set the test program will advance to step 4 STEP 4 Observe the condition of PLC inputs There are actually two stages to this...

Страница 27: ...ndicated by the arrows on the motors If not kill power and reverse two of the leads at the proper motor starter Return to this step in the test program If this is a new installation it will be necessa...

Страница 28: ...e Combustion Air Fan also turns on for 5 seconds at start of this step Turning the switch to turns on the ignition transformer IGT Hold the IGT on for several seconds while observing the flame light o...

Страница 29: ...C SHUTDOWN SETUP DISABLE AND RESET OR ENABLE SET TIME YES AND RESET 4 OBSERVE CONDITION OF INPUTS 0 LOCAL STOP O ON 3 REMOTE STOP O ON 13 HI TEMP LIMIT ON 21 OIL HI PRESSURE ON 5 AIR FLOW SW OFF ON IF...

Страница 30: ...ALVE CENTER TO HOLD POSITION LEFT CLOSES FUEL VALVE RESET AND AIR FLOW ON 8 TEST AND ADJUST ATOMIZING AIR PRESSURE APR AND AAP RESET AND AIR FLOW ON RIGHT OPENS AAV LEFT CLOSES AAV 9 TEST COMBUSTION A...

Страница 31: ...SHIELDED TWISTED PAIR 3 THERMOCOUPLE WIRES AFTER MIX POINT THERMOCOUPLE MARKED BLUE BEFORE MIX POINT HIGH LIMIT THERMOCOUPLE MARKED RED FROM CONSOLE TO ENTRANCE OF TOWER OR SECOND STAGE SKIMMER OUTLE...

Страница 32: ...CONDUIT WITH 2 SHIELDED TWISTED PAIRS WITH SHIELD GROUND WIRE AND 3 16 GA WIRES SHIELDED WIRES CAN BE RAN WITH SENSITIVE WIRES FROM 20000 REMOTE CONTROL 2 16 GA WIRES 8 HOT BOX II TRASH GATE OPEN SWI...

Страница 33: ...PAGE 30 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 34: ...PAGE 31 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 35: ...PAGE 32 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 36: ...PAGE 33 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 37: ...PAGE 34 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 38: ...PAGE 35 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 39: ...PAGE 36 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 40: ...PAGE 37 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 41: ...PAGE 38 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 42: ...PAGE 39 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 43: ...GE 20266 0 100 PSI UPPER CABINET APR AIR PRESSURE REGULATOR 13594A R07 200 RNKA UPPER CABINET BHT BURNER HIGH TEMPERATURE SWITCH 14392 SWITCH UNIT PB 10A 14393 TEMPERATURE TRANS KJ 11A1 UPPER CABINET...

Страница 44: ...L OIL VALVE 16384 M8263B206V LOWER CABINET FP FUEL PUMP 16334 1300099 LOWER CABINET FPG FUEL PRESSURE GAGE 12313 0 160 PSI LOWER CABINET FPR FUEL PRESSURE RELIEF VALVE 12385 VJ 2W WS LOWER CABINET FS...

Страница 45: ...237 BURNER IGT IGNITION TRANSFORMER 20632 1092 F UPPER CABINET LFS LOW FIRE SWITCH 16848 BZE6 2RN80 BURNER LP LOCAL PANEL COMPLETE 20128 SJMC UPPER CABINET MC1 COMBUSTION FAN MOTOR CONTACTOR 14854A LC...

Страница 46: ...SP HO 4 BURNER OPM FUEL PUMP MOTOR 1 3HP 14735 M3458 LOWER CABINET PLC PLC COMPLETE ASSEMBLY 20619 DL 205 UPPER CABINET PV PILOT VALVE 17218 804098 GAS TRAIN CABINET SCR1 FUEL STRAINER 1 4 INCH 09991...

Страница 47: ...PAGE 44 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 48: ...PAGE 45 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 49: ...PAGE 46 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 50: ...PAGE 47 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 51: ...PAGE 48 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 52: ...PAGE 49 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 53: ...PAGE 50 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 54: ...PAGE 51 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 55: ...PAGE 52 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 56: ...PAGE 53 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 57: ...PAGE 54 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 58: ...PAGE 55 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 59: ...PAGE 56 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 60: ...PAGE 57 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 61: ...PAGE 58 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 62: ...PAGE 59 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 63: ...PAGE 60 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED...

Страница 64: ...PAGE 61 of 61 HO 7 1237 HO 4 1234 OIL FIRED HEATERS SAMUEL JACKSON INCORPORATED 2003 ALL RIGHTS RESERVED This page intentionally blank...

Отзывы: