PAGE 23 of 46 HG-1-1501 GAS-FIRED HEATER
© SAMUEL JACKSON, INCORPORATED 2011 ALL RIGHTS RESERVED
Once the VP is within the desirable range, adjust the Air Flow Switch AFS. See picture
below for instructions.
Adjust this screw in (clockwise) until
Input No. X5 on PLC goes off. Slowly
start backing screw out until input 5
comes on then continue to back screw
out
½
more round.
Observe Input No. X5 on PLC for
on/off condition of Air Flow Switch.