PAGE 30 of 41 HG-1-1401A GAS-FIRED HEATER
© SAMUEL JACKSON, INCORPORATED 2005 ALL RIGHTS RESERVED
PROPER GROUNDING
Proper grounding of the Heater control cabinet is essential to the Heater’s continued proper
operation. The Heater’s PLC can loose its program if not properly grounded rendering the Heater
inoperable. For this reason it is recommended that you follow these grounding tips:
•
Always run the ground wire directly to a 6-foot (or longer) earth ground rod.
•
Always use AWG8 aluminum ground wire or better.
•
The earth ground rod should be within 25’ of the heater control cabinet.
•
Do not connect Heater ground to the gin’s common ground.
Grounding of HG-1-1401