Operating Instructions and Installation
3-12
Samsung Electronics
3-2-2(i) Refrigerant Adjustment
3-2-2(j) Flare unt fixing torque
Class
At installation
At service
Outter diameter
ø 6.35 (9000Btu, 12000Btu)
(Liquid Side)
ø 9.52 (9000Btu)
(Gas Side)
ø 12.7 (12000Btu)
(Gas Side)
160
300
500
200
350
550
Fixing Torque Final Torque
Torque (kg-cm)
Connection
Pipe Length
5m Max.
5~10m
Air-Purge
Method
Refer to the
detailed Air-Purge
Procedure
Refrigerant
Adjustment
Unnecessary
Add 10g of refrigerant
(R-22) for every 1m.
Air-Purge
Method
Purge air using a
vaccum pump
or an additional
refrigerant cylinder.
Refrigerant
Quantity
refer to
specification sheet
Add 10g of refrigerant
(R-22) for every 1m.
Содержание US07A1VE
Страница 2: ... Samsung Electronics Co Ltd FEB 1997 Printed in Korea Code No DB81 10122A 1 ...
Страница 4: ...1 2 Samsung Electronics MEMO ...
Страница 27: ...Samsung Electronics 3 14 MEMO ...
Страница 42: ...Samsung Electronics 6 1 6 Exploded Views and Parts List 6 1 Indoor Unit ...
Страница 44: ...Samsung Electronics 6 3 6 2 Outdoor Unit 24 1 24 25 25 2 25 1 25 3 25 4 25 5 18 18 1 19 ...
Страница 48: ...6 7 Samsung Electronics MEMO ...
Страница 50: ...Samsung Electronics 8 1 8 PCB Diagrams 8 1 a Main PCB 7000Btu DB93 10483A ...
Страница 52: ...Samsung Electronics 8 3 8 1 b Main PCB 9000 12000Btu 12000BUT DB93 10471A 9000BUT DB93 10485A ...
Страница 55: ...Samsung Electronics 9 1 9 Wiring Diagrams 9 1 Indoor Unit ...
Страница 57: ...Samsung Electronics MEMO ...
Страница 58: ...Samsung Electronics MEMO ...
Страница 59: ...10 1 10 Schematic Diagrams 10 1 Indoor Unit Samsung Electronics ...
Страница 60: ...Samsung Electronics 10 2 10 2 Remote Control ...