12-4 Main Part Inspection Method
Part
Breakdown Inspection Method
Room Temperature Sensor
Measure resistance with a tester
Normal
At the normal temperature 37kΩ~ 8.3kΩ [19˚F~86˚F(-7˚C~+30˚C)]
*Refer to Table 12-3-4.
Abnormal
∞, 0Ω . . . Open or Short
Room Fan Motor
Measure the resistance between terminals of the connector (CN72) with a tester.
Normal
At the normal temperature [50˚F~86˚F(10˚C~30˚C)]
Abnormal
∞, 0Ω . . . Open or Short
Stepping Motor
Measure the resistance between the red wire and each terminal wire with a tester.
Normal
About 300Ω at the normal temperature [68˚F~86˚F(20˚C~30˚C)]
Abnormal
∞, 0Ω . . . Open or Short
Compare terminal
Resistance
Remark
Yellow, Blue
198Ω ± 10%
Yellow, Red
162Ω ± 10%