Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
Individual control of a
remote controller
Heating setting compensation / Removing
condensate water in heating mode
Adjusted EEV step of
stopped unit during oil
return /defrost mode.
Motion detect sensor
-
Indication
and Details
Indication Details Indication
Details
Indication
Details
Indication
Details
Indication
Details
-
Heating Setting
Compensation
Removing
Condensate
Water in
Heating
Mode
3
0 or 1
channel 1
0
Default
Disuse
0
Default
0
Disuse
1
2 °C
Disuse
1
Turn out in 30min. without motion
2
channel 2
2
5 °C
Disuse
2
Turn out in 60min. without motion
3
Default
Use (*7)
3
Turn out in 120min. without motion
3
channel 3
4
Turn out in 180min. without motion
4
2 °C
Use (*7)
1
Adjusted
EEV
positon
5
Turn out in 30min. without motion
or *advanced function
4
channel 4
6
Turn out in 60min. without motion
& *advanced function
5
5 °C
Use (*7)
7
Turn out in 120min. without motion
& *advanced function
8
Turn out in 180min. without motion
& *advanced function
*
Advanced function: Controlling cooling/heating current or power saving with motion detect.
(*1)
When COOL or dry mode is off. The indoor fan operate in setting minutes.
(*2)
Minimizing fan operation when thermostat is off
- Fan operates for 20 seconds at an interval of 5 minutes in HEAT mode.
- Fan stops or operates Ultra low in Cooling when thermostat is off.
(*3)
1: Fan is turned on continually when the hot water heater is turned on,
3: Fan is turned off when the hot water heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch(MCM-C200) on the outdoor unit and fix it as COOL mode.
If the "Cooling Priority" option is set in the Heat Pump outdoor unit, the indoor unit can operate in the Heat mode owing to the water heater
even if the outdoor unit is running in the Cool mode.
(*4)
When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact control will not be output.
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned off when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch(MCM-C200) on the outdoor unit and fix it as COOL mode.
- If Fan is set to off for cooling only indoor unit by setting the SEG9=3 or SEG15=3, you need to use an external sensor or wired remote
controller sensor to detect indoor temperature exactly.
- If the "Cooling Priority" option is set in the Heat Pump outdoor unit, the indoor unit can operate in the Heat mode owing to the external
heater even if the outdoor unit is running in the Cool mode.
(*5)
When indoor unit is in cooling or Dry mode, The output signal is “ON”
(*6)
For free cooling control, Economizer controller is required.
(*7)
If the air conditioner operates the heating mode immediately after finishing the cooling mode, the condensate water in the drain pan becomes
water vapor by the heat of the indoor unit heat exchanger. Since the water vapor might be condensed on the indoor unit, which may fall into
a living space, use this function to get rid of the water vapor out of the indoor unit by operating the fan (for maximum 20 minutes) even when
the indoor unit is turned off after cooling mode is turned to heating mode .
X
Do not install the electronic heater in the flow channel of the indoor unit fan.
Air Flow
Suction side
Discharge side
Electronic heater should
not be installed.
Duct Indoor unit