Option

SEG19

SEG20

SEG21

SEG22

SEG23

SEG24

Explanation

PAGE

Individual control of a 

remote controller

Heating setting compensation / Removing 

condensate water in heating mode

Adjusted EEV step of 

stopped unit during oil 

return /defrost mode.

Motion detect sensor

-

Indication 

and Details

Indication Details Indication

Details

Indication

Details

Indication

Details

Indication

Details

-

Heating Setting 

Compensation

Removing 

Condensate 

Water in 

Heating 

Mode

3

0 or 1

channel 1

0

Default

Disuse

0

Default

0

Disuse

1

2 °C

Disuse

1

Turn out in 30min. without motion

2

channel 2

2

5 °C

Disuse

2

Turn out in 60min. without motion

3

Default

Use (*7)

3

Turn out in 120min. without motion

3

channel 3

4

Turn out in 180min. without motion

4

2 °C

Use (*7)

1

Adjusted 

EEV 

positon 

5

Turn out in 30min. without motion 
or *advanced function

4

channel 4

6

Turn out in 60min. without motion 
& *advanced function

5

5 °C

Use (*7)

7

Turn out in 120min. without motion 
& *advanced function

8

Turn out in 180min. without motion 
& *advanced function

Advanced function: Controlling cooling/heating current or power saving with motion detect.

(*1)

   When COOL or dry mode is off. The indoor fan operate in setting minutes.

(*2)

   Minimizing fan operation when thermostat is off 

- Fan operates for 20 seconds at an interval of 5 minutes in HEAT mode. 
- Fan stops or operates Ultra low in Cooling when thermostat is off. 

(*3)

   1: Fan is turned on continually when the hot water heater is turned on, 

3: Fan is turned off when the hot water heater is turned on with cooling only indoor unit 
Cooling only indoor unit: To use this option, install the Mode Select switch(MCM-C200) on the outdoor unit and fix it as COOL mode. 
If the "Cooling Priority" option is set in the Heat Pump outdoor unit, the indoor unit can operate in the Heat mode owing to the water heater 
even if the outdoor unit is running in the Cool mode.

(*4)

   When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact control will not be output. 

2: Fan is turned on continually when the external heater is turned on, 
3: Fan is turned off when the external heater is turned on with cooling only indoor unit 
Cooling only indoor unit: To use this option, install the Mode Select switch(MCM-C200) on the outdoor unit and fix it as COOL mode. 
-  If Fan is set to off for cooling only indoor unit by setting the SEG9=3 or SEG15=3, you need to use an external sensor or wired remote 

controller sensor to detect indoor temperature exactly.

-  If the "Cooling Priority" option is set in the Heat Pump outdoor unit, the indoor unit can operate in the Heat mode owing to the external 

heater even if the outdoor unit is running in the Cool mode.

(*5)

   When indoor unit is in cooling or Dry mode, The output signal is “ON”

(*6)

   For free cooling control, Economizer controller is required.

(*7)

   If the air conditioner operates the heating mode immediately after finishing the cooling mode, the condensate water in the drain pan becomes 

water vapor by the heat of the indoor unit heat exchanger. Since the water vapor might be condensed on the indoor unit, which may fall into 
a living space, use this function to get rid of the water vapor out of the indoor unit by operating the fan (for maximum 20 minutes) even when 
the indoor unit is turned off after cooling mode is turned to heating mode .

X

   Do not install the electronic heater in the flow channel of the indoor unit fan. 

Air Flow 

Suction side 

Discharge side 

Electronic heater should 
not be installed. 

Duct Indoor unit 

Содержание Slim 1 Way

Страница 1: ...ioner Installation manual Slim 1 Way cassette Thank you for purchasing this Samsung air conditioner Before operating this unit please read this installation manual carefully and retain it for future r...

Страница 2: ...Purging the Unit 10 Connecting the Refrigerant Pipe 11 Cutting Flaring the Pipes 12 Performing LeakTest Insulation 13 Drain pipe and Drain Hose Installation 15 Bushing Bracket Installation 17 WiringWo...

Страница 3: ...oner contains a refrigerant that has to be disposed of as special waste At the end of its life cycle the air conditioner must be disposed of in authorized centers or returned to the retailer so that i...

Страница 4: ...onditioner may be out of order The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet The copper pipe or connection pipe may corrode and refrigerant may le...

Страница 5: ...pping from the drain hose runs away correctly and safely X The indoor unit must be installed in this way that they are out of public access Not touchable by the users X Rigid wall without vibration X...

Страница 6: ...6 Selecting the Installation Location Space Requirements for Indoor Unit 150 5 9 or more 150 5 9 or more 150 5 9 or more 1500 59 or more Unit mm inch...

Страница 7: ...he indoor unit Unit mm inch Suspension position Ceiling opening Ceiling Drainhole Ceiling opening Suspension position 1150 45 28 1035 8 40 78 249 9 80 440 17 32 21 0 83 77 3 03 52 2 05 50 1 97 85 3 35...

Страница 8: ...mensions between the markings Note 2 Insert bolt anchors use existing ceiling supports or construct a suitable support as shown in figure 3 Install the suspension bolts depending on the ceiling type X...

Страница 9: ...leaks 6 Adjust the height of the indoor unit by using the gauge of dimensions X You should adjust the gauge of dimensions and the pattern sheet to fit the cutting dimensions of ceiling X Make sure tha...

Страница 10: ...arge of nitrogen gas insert gas Therefore all insert gas must be purged before connecting the assembly piping Unscrew the pinch pipe at the end of each refrigerant pipe Result All inert gas escapes fr...

Страница 11: ...5 Must apply refrigerant oil on the flaring area to prevent a leak Note 3 Be sure that there must be no crack or kink on the bended area X Connecttheindoorandoutdoorunitsusingpipeswithflared connectio...

Страница 12: ...inch 6 35 1 4 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 9 52 3 8 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 12 7 1 2 0 0 5 0 0 02 1 0 1 5 0 04 0 06 1 5 2 0 0 06 0 08 15 88 5 8 0 0 5 0 0 0...

Страница 13: ...n the system you can insulate the piping and hose 1 To avoid condensation problems place T13 0 1 2 or thicker Acrylonitrile Butadien Rubber separately around each refrigerant pipe Note Always make the...

Страница 14: ...sand Operation purpose condition Restaurant ceiling sauna swimming pool etc Building construction condition The ceiling frequently exposed to moisture and cooling is not covered e g The pipe installed...

Страница 15: ...lled on the drain hose port X Drain hose port location differs depending on the unit types 3 Install the drain pipe as shortly as possible X Give a slightly slant to the drainpipe for proper drainage...

Страница 16: ...1 1 5m 3 28 4 92 ft 200 7 87 ormore 20 0 79 ormore Ceiling Hanger Centralized Drainage 1 Install main air vent at the front of the farthest indoor unit from the main drain when installed indoor units...

Страница 17: ...k drain water drops at the end of the drainpipe Drainpipe Drain water drops 5 Make sure there is no water leak at the drainage 6 When you finished the test close the coverside Whenmaintainingtheaircon...

Страница 18: ...talling the wired remote Control Power and communication cable connection Norminaldimensionsforcable mm2 inch2 1 5 0 002 2 5 0 003 4 0 006 Norminaldimensionsforscrew mm inch 4 0 15 4 0 15 4 0 15 4 0 1...

Страница 19: ...Distance among each indoor unit m Ak Power cable specification mm2 inch2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Example of Installation Total power cabl...

Страница 20: ...connection from the power supply must be incorporated in the fixed wiring 3mm 1 8 X You must keep the cable in a protection tube X Keep distances of 50mm 2 or more between power cable and communicatio...

Страница 21: ...ethod 2 Twist the wire cores together and push it into the sleeve Connection sleeve Connection sleeve X Ifcablewiresareconnectedwithoutusingconnectingsleeves theircontactarea becomesreduced orcorrosio...

Страница 22: ...h the insulation tape to finish Three or more layers of insulation are required X Method 1 X Method 2 Insulation tape Insulation tape X Make sure that the connection parts are not exposed to outside X...

Страница 23: ...dure of option setting After entering the option setting status select the option as listed below Option setting is available from SEG1 to SEG 24 X SEG1 SEG7 SEG13 SEG19 are not set as page option X S...

Страница 24: ...to enter SEG8 value Each time you press the button will be selected in rotation SEG6 SEG8 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Pr...

Страница 25: ...enter SEG21 value Press High Fan button to enter SEG22 value Each time you press the button will be selected in rotation SEG21 SEG22 18 Setting Heat mode Press Mode button to be change to HEAT mode in...

Страница 26: ...it Theunitdigitofan indoorunit Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 dig...

Страница 27: ...However if the central control is not connected but it doesn t indicate an error message you need to set the central control option as 0 Disuse to exclude the indoor unit from the central control X Th...

Страница 28: ...ing CoolingUltraLow Fan 2 Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Useofdrainpump Useofhotwaterheater EEVStepwhen heatingstops Indication andDetails Indication Details Indication Detai...

Страница 29: ...installtheModeSelectswitch MCM C200 ontheoutdoorunitandfixitasCOOLmode Ifthe CoolingPriority optionissetintheHeatPumpoutdoorunit theindoorunitcanoperateintheHeatmodeowingtothewaterheater eveniftheout...

Страница 30: ...rLongpipeorheight differencebetweenindoor units MTFC 4 Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details 1 0 1 C 0 5min 0 Default 0 D...

Страница 31: ...Nodelay D 6 0 C 10minutes E 6 0 C 20minutes Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 Explanation PAGE ForcingFANOperation forHeatingandCooling Indication andDetails Indication Details Indication Det...

Страница 32: ...ture setintheAutoChangeOverscreenafterenteringtheUsermode bypressingthe buttononthewiredremotecontrol theairconditionerchangesintotheautomaticheatingmode 2 Heightdifference Thedifferenceoftheheightbet...

Страница 33: ...e each digit of set option Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAGE MODE Theoptionmode youwanttochange Thetens digitofan optionSEGyouwill change Theunitdigitofan optionSEGyouwill change C...

Страница 34: ...X Setting the main indoor unit in the S net pro2 a b c d a Select an emergency temperature output ETO mode b Select the main indoor unit c Set the duration used as a reference for generating emergency...

Страница 35: ...r unit c Set the operation mode fan speed and set temperature X Operation when the external contact settings and the ETO settings overlap Mainindoorunit EnableofETO Enableofexternalcontact Errorportou...

Страница 36: ...ect operation follow the steps below After finishing the installation of the air conditioner you should explain the fol lowing to the user Refer to appropriate pages in the User s Manual 1 How to star...

Страница 37: ...for 2 minutes 2 Communication error received from the outdoor unit 3 3 miniute tracking error on outdoor unit 4 Communication error after tracking due to unmatching number of installed units 5 Error...

Страница 38: ...re on discharged air on outdoor unit 2nd detection 6 Indoor operation stop due to unconfirmed error on outdoor unit 7 Error due to reverse phase detection 8 Comp stop due to freeze detection 6th detec...

Страница 39: ...39 ENGLISH MEMO...

Страница 40: ...DB68 03806A 05...

Отзывы: