4. Connecting the adaptor cable

5. Cable Connection

Power Cable

The following table shows maximum distances allowed for 24VAC applications with 

a 10% voltage drop. (10%: The maximum value allowed for AC voltage equipment)

Wire 

Power 

Consumption

AWG #22

AWG #20

AWG #18

AWG #16

AWG #14

AWG #12

AWG #10

30 vA

(indoor)

57ft

(17m)

94ft

(28m)

150ft

(45m)

238ft

(72m)

380ft

(115m)

603ft

(183m)

960ft

(292m)

75 vA

(outdoor)

25ft

(7m)

37ft

(11m)

60ft

(18m)

95ft

(29m)

152ft

(46m)

241ft

(73m)

384ft

(117m)

Communication Cable

Cable requirements for RS-485 communication are as follows:

- Shielded Twisted Pair (STP) Cable

- Low Impedance

- Gauge greater than AWG #22 (0.33

mm

2

)

6. Communication Setup

Camera Address Setup

Use SW606, SW605, and SW604 to specify the camera address.

You can specify between 0 and 255 for the address, where the hundreds digit is 

with SW606, the tens digit with SW605, and the ones digit with SW604.

ex) Camera address: If the address is 1, follow the steps in the fi gure below.

1.

2.

1.

Single pair

Insulating outer cover

Multicore

Adaptor Board

SW606

(x100)

SW605

(x10)

SW604

(x1)

Baud Rate Setup

Use pins #5, #6 of SW603 to set the baud rate.

BAUD RATE

PIN 5

PIN 6

4800 BPS

ON

ON

9600 BPS

OFF

ON

19200 BPS

ON

OFF

38400 BPS

OFF

OFF

The factory default is 9600 BPS.

Caution

The above PIN setting is available only for Samsung protocols.

Termination

If a number of cameras are connected in a daisy chain* confi guration as shown in 

the connection diagrams below, the last camera must be RS-485 terminated by 

using Rx and Tx. (*Daisy Chain: A daisy chain is a means of connecting a number of 

devices to each other in series. For example, Camera 1 is connected to Camera 2, 

and Camera 2 is connected to Camera 3, and so on.)

Communication

Rx

Tx

RS-485 Half Duplex

ON

OFF

RS-422A/RS485 Full Duplex

ON

ON

Connection Diagrams

Although you can connect up to 128 cameras, connecting less than 32 cameras 
ensures the best communication environment.
A communication error may occur if you connect multiple cameras that are assigned 
the same address in the network.

2.

3.

M

Rx(-)    Rx(+)

CAM  1

Data(+)

Data(-)

CONTROLLER

Rx(-)    Rx(+)

CAM  2

Rx(-)    Rx(+)

CAM  n-1

Rx(-)    Rx(+)

CAM  n

Tx(-) Tx(+) Rx(-) Rx(+)

Tx(-) Tx(+) Rx(-) Rx(+)

Tx(-) Tx(+) Rx(-) Rx(+)

Tx(-) Tx(+) Rx(-) Rx(+)

CAM  1

Tx +
Tx -

Rx +

Rx -

CONTROLLER

CAM  2

CAM  n-1

CAM  n

<RS-485 Half Duplex>

<RS-422A/RS485 Full Duplex>

3. At a Glance

CAMERA

FRAME SET

Wipe out a dirty surface of the lens softly with a lens tissue or cloth to which you 
have applied ethanol.

M

ALARM IN

POWER INPUT

RS-485

ALARM OUT

LENS

HOOK

HOOK