4. Connecting the adaptor cable
5. Cable Connection
Power Cable
The following table shows maximum distances allowed for 24VAC applications with
a 10% voltage drop. (10%: The maximum value allowed for AC voltage equipment)
Wire
Power
Consumption
AWG #22
AWG #20
AWG #18
AWG #16
AWG #14
AWG #12
AWG #10
30 vA
(indoor)
57ft
(17m)
94ft
(28m)
150ft
(45m)
238ft
(72m)
380ft
(115m)
603ft
(183m)
960ft
(292m)
75 vA
(outdoor)
25ft
(7m)
37ft
(11m)
60ft
(18m)
95ft
(29m)
152ft
(46m)
241ft
(73m)
384ft
(117m)
Communication Cable
Cable requirements for RS-485 communication are as follows:
- Shielded Twisted Pair (STP) Cable
- Low Impedance
- Gauge greater than AWG #22 (0.33
mm
2
)
6. Communication Setup
Camera Address Setup
Use SW606, SW605, and SW604 to specify the camera address.
You can specify between 0 and 255 for the address, where the hundreds digit is
with SW606, the tens digit with SW605, and the ones digit with SW604.
ex) Camera address: If the address is 1, follow the steps in the fi gure below.
1.
2.
1.
Single pair
Insulating outer cover
Multicore
Adaptor Board
SW606
(x100)
SW605
(x10)
SW604
(x1)
Baud Rate Setup
Use pins #5, #6 of SW603 to set the baud rate.
BAUD RATE
PIN 5
PIN 6
4800 BPS
ON
ON
9600 BPS
OFF
ON
19200 BPS
ON
OFF
38400 BPS
OFF
OFF
The factory default is 9600 BPS.
Caution
The above PIN setting is available only for Samsung protocols.
Termination
If a number of cameras are connected in a daisy chain* confi guration as shown in
the connection diagrams below, the last camera must be RS-485 terminated by
using Rx and Tx. (*Daisy Chain: A daisy chain is a means of connecting a number of
devices to each other in series. For example, Camera 1 is connected to Camera 2,
and Camera 2 is connected to Camera 3, and so on.)
Communication
Rx
Tx
RS-485 Half Duplex
ON
OFF
RS-422A/RS485 Full Duplex
ON
ON
Connection Diagrams
Although you can connect up to 128 cameras, connecting less than 32 cameras
ensures the best communication environment.
A communication error may occur if you connect multiple cameras that are assigned
the same address in the network.
2.
3.
M
Rx(-) Rx(+)
CAM 1
Data(+)
Data(-)
CONTROLLER
Rx(-) Rx(+)
CAM 2
Rx(-) Rx(+)
CAM n-1
Rx(-) Rx(+)
CAM n
Tx(-) Tx(+) Rx(-) Rx(+)
Tx(-) Tx(+) Rx(-) Rx(+)
Tx(-) Tx(+) Rx(-) Rx(+)
Tx(-) Tx(+) Rx(-) Rx(+)
CAM 1
Tx +
Tx -
Rx +
Rx -
CONTROLLER
CAM 2
CAM n-1
CAM n
<RS-485 Half Duplex>
<RS-422A/RS485 Full Duplex>
3. At a Glance
CAMERA
FRAME SET
Wipe out a dirty surface of the lens softly with a lens tissue or cloth to which you
have applied ethanol.
M
ALARM IN
POWER INPUT
RS-485
ALARM OUT
LENS
HOOK