51
Indoor Unit Control (Continued)
3
When there is a device that supports cooling/heating discharge temperature control
within the selected devices, discharge temperature control part will be activated.
Ex) When S-NET mini is connected to centralized controller and Fresh Duct is
selected with its power on and operating in either cooling or heating mode.
Tap [
▲
][
▼
] to adjust the desired temperature
Each time you tap the button, temperature will be adjusted in 1°C unit.
4
When there is a device that supports Auto Clean function, [Auto Clean] button
will be activated.
If you tap the [Auto Clean] button, function will turn on/off.
5
When there is a device that supports Human Sensor function, [Human Sensor]
button will be activated.
If you tap the [Human Sensor] button, function will turn on/off.
6
When there is a device that supports SPI function, [SPI] button will be
activated.
If you tap the [SPI] button, function will turn on/off.
7
When there is a device that supports OA Intake function, [OA Intake] button
will be activated.
If you tap the [OA Intake] button, function will turn on/off.
Cooling/Heating discharge temperature control is only available when
S-NET mini is connected to the transmitter.
Caution
Model
Cooling/Heating discharge temperature setup
Fresh Duct, MINI AHU
O
EHP, GHP, AHU, Global 4way, ERV, ERV+
X
Model
Heating discharge temperature Cooling discharge temperature
Fresh Duct
18℃ ~ 30℃(65˚F~86˚F)
15℃ ~ 25℃(59˚F~77˚F)
MINI AHU
30℃ ~ 43℃(86˚F~110˚F)
8℃ ~ 18℃(47˚F~65˚F)
Note
Following is the range of cooling/heating discharge temperature setting.
MST-S3W_IB_E_30577-3.indd 51
2011-07-26 오전 9:47:54