Check Mode
E-
27
ENGLISH
View Mode
If you press KEY 4, the display shows you temperature and cycle data
according to number of times. Refer to the table below.
1
2
3
4
5
6
7
8
9
10
11
12
Data of high pressure
Data of low pressure
Outlet temperature of PWM
compressor (Discharge)
Condensation temperature
Outdoor temperature
Steps of electronic expansion
valve
Temperature of COND OUT
Temperature of OIL
Temperature of SUCTION
Steps of outdoor fan
Discharge temperature of fixed
compressor
Stopping of View mode
Displaying communication data
SEG 1 : Flickers with 1
SEG 2, 3, 4: Display data
SEG 1 : Flickers with 2
SEG 2, 3, 4: Display data
SEG 1 : Flickers with 3
SEG 2, 3, 4: Display data
SEG 1 : Flickers with 4
SEG 2, 3, 4: Display data
SEG 1 : Flickers with 5
SEG 2, 3, 4: Display data
SEG 1 : Flickers with 6
SEG 2, 3, 4: Display data
SEG 1 : Flickers with 7
SEG 2, 3, 4: Display data
SEG 1 : Flickers with 8
SEG 2, 3, 4: Display data
SEG 1 : Flickers with 9
SEG 2, 3, 4: Display data
SEG 1 : Flickers with A
SEG 2, 3, 4: Display data
SEG 1 : Flickers with B
SEG 2, 3, 4: Display data
SEG 1, 2 : Display communication data
SEG 3, 4: Off
Displayed up to the 1st
decimal place
Displayed up to the
1st decimal place
-
-
-
-
-
-
-
-
-
-
21.2kg/cm
2
(SEG 2: 2, SEG 3: 1, SEG 4: 2)
8.2kg/cm
2
(SEG 2: Off, SEG 3: 8, SEG 4: 2)
101°C
(SEG 2: 1, SEG 3: 0, SEG 4: 1)
101°C
(SEG 2: 1, SEG 3: 0, SEG 4: 1)
15°C
(SEG 2: Off, SEG 3: 1, SEG 4: 5)
100 STEP
(SEG 2: 1, SEG 3: 0, SEG 4: 0)
-10°C
(SEG 2: -, SEG 3: 1, SEG 4: 0)
22°C
(SEG 2: Off, SEG 3: 2, SEG 4: 2)
22°C
(SEG 2: Off, SEG 3: 2, SEG 4: 2)
12 STEP
(SEG 2: Off, SEG 3: 1, SEG 4: 2)
101°C
(SEG 2: 1, SEG 3: 0, SEG 4: 1)
-
Number of
press times
Contents
Display
Remark
Example
Pressing KEY 1 : Adding refrigerant for heat pump models - Test operation
for heat pump models - Operation with no function.
◆
SEG 1, 2: Display communication status
◆
SEG 3, 4: Flicker with an appropriate KEY function
1
Pressing KEY 2 : Adding refrigerant for cooling only models - Test operation
for cooling only models - Operation with no function
◆
SEG 1, 2: Display communication status
◆
SEG 3, 4: Flicker with an appropriate KEY function
2
Pressing KEY 3 : Reset & tracking
◆
SEG 1, 2: Display communication status
◆
SEG 3, 4: Off
3