48
Cylinder unit
Wiring diagram
•
Turn on the cylinder unit and outdoor unit after completing electric wiring works.
•
Do not disassemble the wirings out of the unit while the unit is operating.
•
Circuit breaker shall be installed for safety and maintenance .
•
Fill the cylinder unit with water before turning on electric power.
CAUTION
f
Make sure of an earthing.
- Do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire. If earthing is incomplete,
electric shock or fire may occur.
1
40.4
66T
59T
2
42.52
50.8
63.5
1
2
L
N
Date code
Cal lot No.
59T 4117
ø5.56
2 holes
Outer casing
Wiring diagram
Electrical connections – Technical Data:
Electric element
2.6 kW 230V 1 phase, 1 1/4” connection with O-ring seal
Adjustable
Electric output can be reduced by cutting one bridge on the element.
Thermostat
40~70°C (preset 60°C)
Safety cut-off
85°C
Electric central
Internally connected from factory. Splash proof IP21.
Electric immersion heater shall comply with EN 60335-2-73
EHS mono_RC***MHXGA_IM_E_34411A(3).indd 48