32
I&O manual
Fig.9-4
Center distan
ce
16mm deflection
per 1 metr
e of
span
Belt tension indicator
applied to mid_center distance
For reguired to deflection belt 16 mm per metre of span
Belt section
SPA
SPB
80 to132
140 to 224
25 to 35
45 to 65
2.5 to 3.6
4.6 to 6.6
Small pulley
diameter (mm)
Newton(N)
Kilogram-force(kgf)
Tab.9-2
NOTE
The belt which is too tight or too loose may generate noise
and be harmful to the unit.
Regulating belt of rate of tension, inner fan
Refer to
Fig.9-3
, Fixed bolt of electric motor’s supporting slide
was loosened, following electric motor was drived, belt of rate
of tension will begin change.
Method of belt tensioning using belt tension indicator
Calculate the deflection in mm on a basis of 16mm per meter
of center distance .Center distance (m)×16=deflection (mm).
Fig.9-3
bolts
Dismantle the air filter.
Twist of screws and up the plate that is gets out.
Upon loose the filter-baffle-plate, the filter could be pulled out
along the supporting slot.
Fig.9-6
●
●
plate
air filter
filter-Baffle-plate
For 6-20 tons
filter-Baffle-plate
air filter
filter access door
For 25 tons
Fig.9-5