Tracking Your Indoor Unit from the Wired Remote Controller

1.  Tracking of your Wired Remote Controller will automatically start when you turn on the power after installation.

2.  If you want to perform tracking again after installation, then press the 

Esc

 and 

Delete

 buttons at the same time 

for more than five seconds.

  

  The system will reset, and tracking will start again.

3.  During tracking, the total number of currently searched indoor units and ventilator(ERV) will be displayed.

4.   It may take about 5 minutes at initial installation or when you re-set the Master setting.

•   If you want to perform tracking again after installation, then press the 

Esc

 and 

Delete

 buttons at the same time 

for more than five seconds.

Displays the total number 

of units searched

Indicates tracking 

in progress

NASA_Wired Remote Control_MWR-WE10N_EN_IM_03716A(1).indd   7

2013-02-01   오후 6:34:07

Содержание MWR-WE10N

Страница 1: ...NASA_Wired Remote Control_MWR WE10N_EN_IM_03716A 1 indd 24 2013 02 01 오후 6 34 12 ...

Страница 2: ...installation manual imagine the possibilities ThankyouforpurchasingthisSamsungproduct This manual is made with 100 recycled paper EN PT ES DE FR EL IT RU AR DB68 03716A 1 NASA_Wired Remote Control_MWR WE10N_EN_IM_03716A 1 indd 25 2013 02 01 오후 6 34 13 ...

Страница 3: ... the product may fall down and it may cause product damage Do not move or reinstall the product on your discretion Potential risk of electric shock or fire Check if the installation work is done correctly according to the installation manual Incorrect installation may cause electric shock or fire When you want to dispose your Wired Remote Controller ask the service center This installation manual ...

Страница 4: ...r product damage Do not install the product in areas exposed to oil or vapor Potential risk of product damage or malfunction Do not put undue stress on the power cable Potential risk of broken cable and fire Do not install the product in areas with frequent use of acid or alkali spray Potential risk of electric shock or product malfunction Do not connect power cable to a communication terminal Pot...

Страница 5: ...ler Install theWired Remote Controller cables in accordance with the electrical wiring rules and allow it to pass through the inner area of the wall so that other people can t reach it 120 0 4 72 124 0 4 88 63 8 2 51 19 5 0 76 Unit mm inch Wired Remote Controller 1 CableTie 2 Cable Clamp 3 M4X16 Screw 5 User Manual 1 Installation Manual 1 UTerminal 4 NASA_Wired Remote Control_MWR WE10N_EN_IM_03716...

Страница 6: ...e the power cable and the communication cable so that they fit in the housing along the edges of the rear cover Insert a flat head screwdriver into the square groove in the upper area of the hook to disassemble it easily When the cable is not concealed When the cable is concealed 15cm 6inch 10cm 4inch If you need more space for the wiring work you can take it off NASA_Wired Remote Control_MWR WE10...

Страница 7: ...ression ring terminal connected to yourWired Remote Controller PCB W t G E F L Stud D RangeofPermittedWires Rated Size Stud Size BasicSize mm inch AWG mm2 inch2 mm2 inch2 mm inch t øD G E F W L 22 16 0 25 1 65 0 0003 0 0025 1 5 0 0023 3 0 1181 0 7 0 0275 3 8 0 1496 10 0 0 3937 4 5 0 1771 6 5 0 2559 6 0 0 2362 21 2 0 8346 Maximum distance for connecting communication and power cable 100 m 3 280 ft ...

Страница 8: ... will reset and tracking will start again 3 During tracking the total number of currently searched indoor units and ventilator ERV will be displayed 4 It may take about 5 minutes at initial installation or when you re set the Master setting If you want to perform tracking again after installation then press the Esc and Delete buttons at the same time for more than five seconds Displays the total n...

Страница 9: ...it or ventilator ERV Wired Remote Controller Installation When Connected to an Indoor Unit Only When Connected to an ventilator ERV Only Outdoor Unit IndoorUnit COM1 F1 F2 COM2 F3 F4 COM1 F1 F2 COM2 F3 F4 COM2 F3 F4 Wired Remote Controller Wired Remote Controller Wired Remote Controller IndoorUnit IndoorUnit Regardless of the indoor group address RMC address or the ventilator ERV group address onl...

Страница 10: ...r to control two or more indoor units and ventilator ERV at the same time When Connected to an Indoor Unit Only Regardless of the indoor unit s group address RMC address only the indoor units connected to COM2 are controlled in group Regardless of your outdoor units you can control a maximum of 16 indoor units as a group 1 Using One Wired Remote Controller to control three indoor Units 2 Using One...

Страница 11: ... 4 Wired Remote Controller COM2 F3 F4 Master ventilator ERV COM1 F1 F2 Ventilator ERV Ventilator ERV Ventilator ERV COM1 F1 F2 COM2 F3 F4 COM1 F1 F2 Regardless of the ventilator ERV s group address RMC address only the ventilator ERV connected to COM2 controlled in group NASA_Wired Remote Control_MWR WE10N_EN_IM_03716A 1 indd 10 2013 02 01 오후 6 34 08 ...

Страница 12: ...er in group you can control maximum of 16 indoor units and ventilator ERV If you want to use the power saving function you have to connectWired Remote Controller to only one indoor unit and one ventilator ERV 1 Using One Wired Remote Controller to control multiple indoor units and ventilator ERV 2 Using One Wired Remote Controller to control indoor units connected to different outdoor unit and ven...

Страница 13: ... controlling one indoor unit ventilator ERV or one group of indoor units and ventilator ERV with two remote controllers When Connected to an Indoor Unit Only When Connected to an ventilator ERV Only For the slaveWired Remote Controller settings please refer to the sections about the additional functions of the Wired Remote Controller Refer to page20 0 Master 1 Slave Wired Remote Controller Install...

Страница 14: ...ERV Together Regardless of the indoor unit group address RMC address only the indoor units connected to COM2 are controlled by 2 remote controller For the slaveWired Remote Controller settings please refer to the sections about the additional functions of the Wired Remote Controller Refer to page20 0 Master 1 Slave NASA_Wired Remote Control_MWR WE10N_EN_IM_03716A 1 indd 13 2013 02 01 오후 6 34 09 ...

Страница 15: ...ntilator ERV then you need to initialize your remote controller communication Wired Remote Controller Installation 1 Press the Esc and Delete buttons at the same time for more than five seconds Your Wired Remote Controller will be initialized and the device will search for the indoor units ventilator ERV connected to your Wired Remote Controller again NASA_Wired Remote Control_MWR WE10N_EN_IM_0371...

Страница 16: ...ed by the error code Example Error 101 occurs for Indoor Unit No 200012 Ventilator ERV When an Error Occurs inYour Ventilator ERV Product Group Display B The product address for the error will be displayed followed by the error code Example Error 121 has occurred at ventilator ERV No 300012 When an Error Occurs inYour Wired Remote Controller Only an error code will be displayed No address will be ...

Страница 17: ...h device Setting Cancelling the Mode master indoor unit Mode master indoor unit setting is simply selecting an indoor unit that will become standard among many indoor units to prevent mixed operation which one or more indoor units operating in different operation mode Setting Connect just 1 indoor unit and stop the operation Then press and hold the Mode button for 5 seconds to set the indoor unit ...

Страница 18: ...n Menu Sub menu 1 2 3 5 4 6 Data bit Additional Functions ofYourWired Remote Controller Wired Remote Controller Installation Service Mode NASA_Wired Remote Control_MWR WE10N_EN_IM_03716A 1 indd 17 2013 02 01 오후 6 34 11 ...

Страница 19: ...a sub menu number and press the button to enter data setting screen When you enter the setting stage the current setting will be displayed Refer to the chart for data settings Using the buttons select the settings Press the button to move to the next setting Press the Set button to save the settings and exit to the sub menu setting screen Press the Esc button to exit to normal mode While setting t...

Страница 20: ...ode 3 0 0 Nouse 1 Use Useofexternalcontrol 4 0 0 Nouse 1 Use 5 RoomTemperature compensation Temperaturecontrolreference 1 2 3 0 9 40 C 15 104 F 0 1 C Temperaturecompensationvalue 4 5 6 0 9 9 9 9 C 0 1 C 6 Numberofconnectedunits Numberofindoorunits 1 2 0 16 NumberofERVs 3 4 0 16 7 Temperatureincrement decrement Conly 1 0 0 1 C 1 0 5 C 2 0 1 C 8 Set CheckERVEnergysaving operation SelectindividualEne...

Страница 21: ...ing checking 6 0 30 1 40 2 50 2 Indoorunit AHUdischarge temperaturesetting checking Useofdischarge temperaturecontrol 1 0 Nouse 1 Use Coolingdischargetemperature 3 4 8 18 C 46 64 F 1 C Heatingdischargetemperature 5 6 30 43 C 86 109 F 1 C 3 FreshDuctdischarge temperaturechecking Coolingdischargetemperature 1 2 15 25 C 59 77 F 1 C Heatingdischargetemperature 3 4 18 30 C 64 86 F 1 C 6 1 ERVPlussettin...

Страница 22: ...er SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 1 Page number SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 2 Page number SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Page number Regardless of Celsius and Fahrenheit setting service mode setting is available only with Celsius Main menu Sub menu Function Data bit Factory setting Description Unit 7 1 Mastersetting checking F3F4lineIndoorunitmaster IndoorunitMastersetting checkin...

Страница 23: ...o select the desired Data1 Press button to select no 1 The wired remote controller option is set from both cooling and heating to cooling only 5 Press Set button to complete the option setting Save the setting value and exit to sub menu 6 Press Esc button to exit to normal mode 1 2 3 4 Data bit Data1 Both cooling and heating of an indoor unit Data2 Use wireless remote controller Data3 Master wired...

Страница 24: ...ENGLISH 23 Memo NASA_Wired Remote Control_MWR WE10N_EN_IM_03716A 1 indd 23 2013 02 01 오후 6 34 12 ...

Отзывы: