E-
62
Message Definition (Continued)
Description
1. Remote control restriction status
2. Filter alert status
3. Thermo On/Off status
4. Error alert Status
SNVT Type
SNVT_state: 16 Unsigned Bitfields
Value and operation
Byte
Bit9
Bit8
Operation
Remark
Flags_1
0
0
Unlock
nvoUserLockout
0
1
Level1
1
0
Lock
Byte
Bit
value
Operation
Remark
Flags_2
2
0
No alarm
nvoFilterAlarm
1
Alarm
1
0
Thermo Off
Thermo On/Off
1
Thermo On
0
0
No Error
nvoErrorCode
1
Error
nvoDeviceAlarm(18)
Description
Operation Mode restriction
SNVT Type
SNVT_switch: Unsigned/singed Short
Value and operation
Value
State
Unlock
0.0
0
Cool only
1.0
1
Heat only
2.0
1
nvoOccOpMode(19), nviOccOpModeCmd(8)
Description
Setting/monitoring Lower limit temperature
and function toggle
SNVT Type
SNVT_switch: Unsigned/singed Short
Value and operation
Operation
Value
State
Unlock
18.0 ~ 30.0
0
Lock
18.0 ~ 30.0
1
Cool: 18.0°C ~ 30.0°C
nvoCoolTempLock(20), nviCoolTempLock(9)