![Samsung MH040FXEA2C Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/samsung/mh040fxea2c/mh040fxea2c_installation-manual_4743418005.webp)
E-
6
PREPARING THE INSTALLATION
Deciding on Where to Install the Air Conditioner (Continued)
MH050FX
A2B/MH050FX
A2C
Indoor unit
Outdoor unit
Power supply
Ø, V, Hz
020/023/026/035/052
MH050FX
A2B
MH050FX
A2C
1,220-240, 50
Unit
Outside diameter
Liquid
Gas
020/023/026/035
1/4"
3/8"
052
1/2"
MH050FX
A2B/MH050FX
A2C outdoor unit cannot be connected to the following indoor unit combination.
-MH052FMEA/MH052FUEA
Piping outside diameter
(h)
(H)
A
B
600 mm
minimum
1 Room max
length
2 Room total max
length
Max height between
indoor unit & outdoor unit
Max height between
indoor units
Dimension
20m
30 m
15m
7.5 m
Composition
A,B
A+B
(H)
(h)
Piping length and the height
Main power switch
200 mm
or more
160 mm
or more
100 mm
or more
300 mm
minimum
300 mm
minimum
600 mm
minimum
CAUTION:
3 m as minimum pipe length: It will reduce
noise and vibration.
This value must be increased at 7.5 meters
in case it is connected just one indoor unit.
System can work with one indoor unit connected, but it is recommended that the TOTAL number
of indoor unit suggested by manufacturer are connected to obtain the maximum performance.
The appearance of the unit may be different from the diagram depending on the model.
Make at least one round:
It will reduce noise and vibration
The appearance of the unit may be different from the diagram depending on the model.
09'FJM_OUTDOOR_28896A_IM_E_11.23.09.indd 6
2009-11-24 9:19:26