8
Installing the product
Selecting a compressed terminal (Specifi cation for connecting power supply of an indoor unit)
1. Select a solderless ring terminal for a power cable according to the nominal dimensions for cable.
2. Apply insulation coating to the connection part of the solderless ring terminal and the power cable.
Silver solder
Nominal dimensions for cable
1.5
2.5
4
Nominal dimensions for screw
4
4
4
4
4
B
Standard dimension
6.6
8
6.6
8.5
9.5
Allowance
±0.2
±0.2
±0.2
D
Standard dimension
3.4
4.2
5.6
Allowance
+0.3
-0.2
+0.3
-0.2
+0.3
-0.2
d1
Standard dimension
1.7
2.3
3.4
Allowance
±0.2
±0.2
±0.2
E
Minimum
4.1
6
6
F
Minimum
6
6
5
L
Maximum
16
17.5
20
d2
Standard dimension
4.3
4.3
4.3
Allowance
+0.2
0
+0.2
0
+0.2
0
t
Minimum
0.7
0.8
0.9
Setting indoor unit installation option
f
f
To use the Multi Tenant Function Controller, installation option must be changed.
f
f
SEG2 of the installation option on installed indoor units must be set to '5' and SEG11 must be set to '2'.
❋
❋
SEG11: 0 (Disable Multi Tenant Function Controller) / 2 (Enable Multi Tenant Function Controller)
❋
❋
For detail information on the method of setting the installation option, please refer to the indoor unit installation manual.
• Wired remote controller for group control cannot be installed to an indoor unit which Multi Tenant Function
controller was installed.
• EEV operation of the stopped Heat mode will be controlled in same condition as noise reduction control
option (0/80 option) when Multi Tenant Function Controller operates.
• If the Multi Tenant Function Controller operates while multiple indoor units are working in mixed operation
mode (cooling and heating at the same time), dew may form on the indoor unit fan.
CAUTION